Current Ratings & Volt Drop – IEE
TABLE 4A2 Schedule of appropriate current ratings tables - IEE
Specification number | Specification Title | Applicable Current Rating Tables | Conductor Operating Temperature |
BS5467:1997 | Specification for 600/1000V & 1900/3300V armoured electric cables having thermosetting insulation | 4E3, 4E4, 4L3, 4L4 | 90ºC |
BS6004:2000 | Electric cables. PVC insulated, non-armoured cables for voltages up to and including 450/750V, for electric power, lighting & internal wiring | 4D1, 4D2, 4E1 | 70ºC, 90ºC |
PVC insulated & sheathed flat cable with protective conductor to Table 8 | 4D5 | 70ºC | |
BS6207-1:1995 | Mineral insulated cables with a rated voltage not exceeding 750V | 4J1, 4J2 | 70ºC*, 105ºC* |
BS6346:1997 | Specification for 600/1000V & 1900/3300V armoured electric cables having PVC insulation | 4D3, 4D4, 4K3, 4K4 | 70ºC |
BS6500:2000 | Electric cbales. Flexible cords rated up to 300/500V, for use with appliances and equipment intended for domestic, office and similar environments | 4H3 | 60ºC, 90ºC |
BS6724:1997 | Specification for 600/1000V & 1900/3300Varmoured electric cables having thermosetting insulation and low emission of smoke and corrosive gases when affected by fire | 4E3, 4E4, 4L3, 4L4 | 90ºC |
BS6883:1999 | Elastomer insulated cables for fixed wiring in ships and on mobile & fixed offshore units. Requirements & test methods | 4F1, 4F2 | 85ºC |
BS7211:1998 | Specification for thermosetting insulated cables (non-armoured) for electric power & lighting with low emission of smoke & corrosive gases when affected by fire | 4E1, 4E2 | 90ºC |
BS7629-1:1997 | Specification for 300/500V fire resistant electric cables having low emission of smoke & corrosive gases when affected by fire. Multicore cables | 4D2 | 70ºC |
BS7846:2000 | Electric cables. 600/1000V armoured fire-resistant electric cables having thermosetting insulation & low emission of smoke and corrosive gases when affected by fire | 4E4 | 90ºC |
BS7889:1997 | Specification for 600/1000V single-core unarmoured electric cables having thermosetting insulation | 4E1, 4L1 | 90ºC |
BS7919:2001 | Electric cables. Flexible cables rated up to 450/750V, for use with appliances & equipment intended for industrial & similar environments | 4H1, 4H2, 4H3 | 60ºC, 110ºC |
BS8436:2004 | 300/500V screened electric cables having low emission of smoke & corrosive gases when affected by fire, for use in thin partitions and building voids | 4D2 | 70ºC |
BSEN60702-1:2001 | Mineral insulated cables and their terminations with a rated voltage not exceeding 750V. Cables | 4J1, 4J2 | 70ºC*, 105ºC* |
* sheath operating temperature |
TABLE 4A3 Schedule of appropriate current ratings tables - IEE
Specification Number | Specification Title | Applicable Current Rating Tables (16th edition tables) | Conductor Operating Temperature |
BS5467:1997 | Electric cables – thermosetting insulated armoured cables for voltages of 600/1000V & 1900/3300V | 4E3, 4E4, 4J3, 4J4 (4L3, 4L4) | 90ºC |
BS6004:2000 | Electric cables – PVC insulated, non-armoured cables for voltages up to and including 450/750V, for electric power, lighting & internal wiring | 4D1, 4D2 | 70ºC |
Thermoplastic insulated & sheathed flat cable with protective conductor to Table 8 | 4D5 | 70ºC | |
BS6231 | Electic cables – single-core PVC insulated flexible cables of rated voltage 600/1000Vfor switchgear & controlgear wiring | 4D1 | 70ºC* |
BS6346:1997 | Electric cables – PVC insulated, armoured cables for voltages of 600/1000V & 1900/3300V | 4D3, 4D4, 4H3, 4H4 (4K3, 4K4), 4J3, 4J4 | 70ºC |
BS6500:2000 | Electric cbales – Flexible cords rated up to 300/500V, for use with appliances and equipment intended for domestic, office and similar environments | 4F3 (4H3) | 60ºC, 90ºC |
BS6724:1997 | Electric cables – thermosetting insulated, armoured cables for voltages of 600/1000V & 1900/3300V having low emission of smoke and corrosive gases when affected by fire | 4E3, 4E4, 4J3, 4J4 (4L3, 4L4) | 90ºC |
BS7211:1998 | Electric cables – thermosetting insulated non-armoured cables for voltages up to and including 450-750V for electric power, lighting & internal wiring and having low emission of smoke & corrosive gases when affected by fire | 4E2 | 90ºC |
BS7629-1:1997 | Specification for 300/500V fire resistant electric cables having low emission of smoke & corrosive gases when affected by fire. Multicore cables | 4D2 | 70ºC |
BS7846:2000 | Electric cables – 600/1000V armoured fire-resistant electric cables having thermosetting insulation & low emission of smoke and corrosive gases when affected by fire | 4E3, 4E4, 4J3, 4J4 | 90ºC |
BS7889:1997 | Electric cables – thermosetting insulated, armoured cables for a voltatge of 600/1000V | 4E1 | 90ºC |
BS7919:2001 | Electric cables – Flexible cables rated up to 450/750V, for use with appliances & equipment intended for industrial & similar environments | 4F1, 4F2, 4F3, (4H1, 4H2, 4H3) | 60ºC, 90ºC |
BS8436:2004 | Electric cables – 300/500V screened electric cables having low emission ofsmoke & corrosive gases when affected by fire, for use in walls, partitions and building voids – multicore cables | 4D2 | 70ºC |
BSEN60702-1:2001 | Mineral insulated cables and their terminations with a rated voltage not exceeding 750V. Cables | 4G1, 4G2 (4J1, 4J2) | 70ºC**, 105ºC** |
* cables to BS6231 when installed in conduit or trunking are rated to 70ºC | |||
** sheath operating temperature |
Table 4D1A PVC Insulation / Copper / Single-core / Non-armoured - IEE
- Standard: BS 7671
- Table 4D1A
- Single-core 70 °C thermoplastic insulated cables, non armoured, with or without sheath
- Copper conductors
- Conductor temperature: 70 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Reference Method A (enclosed in conduit in thermally insulated wall etc.) | Reference Method B (enclosed in conduit on a wall or in trunking etc.) | Reference Method C (Clipped direct) | Reference Method F (in free air or in perforated cable tray horizontal or vertical) | ||||||||
Touching | Spaced by one diameter | ||||||||||
2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC flat | 3 cables, three- phase AC flat | 3 cables, three- phase AC trefoil | 2 cables single-phase AC or DC or 3 cables three-phase AC flat | ||
Horizontal | Vertical | ||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
1 | 11 | 10.5 | 13.5 | 12 | 15.5 | 14 | – | – | – | – | – |
1.5 | 14.5 | 13.5 | 17.5 | 15.5 | 20 | 18 | – | – | – | – | – |
2.5 | 20 | 18 | 24 | 21 | 27 | 25 | – | – | – | – | – |
4 | 26 | 24 | 32 | 28 | 37 | 33 | – | – | – | – | – |
6 | 34 | 31 | 41 | 36 | 47 | 43 | – | – | – | – | – |
10 | 46 | 42 | 57 | 50 | 65 | 59 | – | – | – | – | – |
16 | 61 | 56 | 76 | 68 | 87 | 79 | – | – | – | – | – |
25 | 80 | 73 | 101 | 89 | 114 | 104 | 131 | 114 | 110 | 146 | 130 |
35 | 99 | 89 | 125 | 110 | 141 | 129 | 162 | 143 | 137 | 181 | 162 |
50 | 119 | 108 | 151 | 134 | 182 | 167 | 196 | 174 | 167 | 219 | 197 |
70 | 151 | 136 | 192 | 171 | 234 | 214 | 251 | 225 | 216 | 281 | 254 |
95 | 182 | 164 | 232 | 207 | 284 | 261 | 304 | 275 | 264 | 341 | 311 |
120 | 210 | 188 | 269 | 239 | 330 | 303 | 352 | 321 | 308 | 396 | 362 |
150 | 240 | 216 | 300 | 262 | 381 | 349 | 406 | 372 | 356 | 456 | 419 |
185 | 273 | 245 | 341 | 296 | 436 | 400 | 463 | 427 | 409 | 521 | 480 |
240 | 321 | 286 | 400 | 346 | 515 | 472 | 546 | 507 | 485 | 615 | 569 |
300 | 367 | 328 | 458 | 394 | 594 | 545 | 629 | 587 | 561 | 709 | 659 |
400 | – | – | 546 | 467 | 694 | 634 | 754 | 689 | 656 | 852 | 795 |
500 | – | – | 626 | 533 | 792 | 723 | 868 | 789 | 749 | 982 | 920 |
630 | – | – | 720 | 611 | 904 | 826 | 1005 | 905 | 855 | 1138 | 1070 |
800 | – | – | – | – | 1030 | 943 | 1086 | 1020 | 971 | 1265 | 1188 |
1000 | – | – | – | – | 1154 | 1058 | 1216 | 1149 | 1079 | 1420 | 1337 |
Table 4D2A PVC Insulation / Copper / Multi-core / Non-armoured - IEE
- Standard : BS 7671
- Table 4D2A
- Multi-core 70 °C thermoplastic insulated and thermoplastic sheathed cables, non armoured
- Copper conductors
- Conductor temperature: 70 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | |||||||
---|---|---|---|---|---|---|---|---|
Reference Method A (enclosed in conduit in thermally insulated wall etc.) | Reference Method B (enclosed in conduit on a wall or in trunking etc.) | Reference Method C (Clipped direct) | Reference Method E (in free air or in perforated cable tray horizontal or vertical) | |||||
1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
1 | 11 | 10 | 13 | 11.5 | 15 | 13.5 | 17 | 14.5 |
1.5 | 14 | 13 | 16.5 | 15 | 19.5 | 17.5 | 22 | 18.5 |
2.5 | 18.5 | 17.5 | 23 | 20 | 27 | 24 | 30 | 25 |
4 | 25 | 23 | 30 | 27 | 36 | 32 | 40 | 34 |
6 | 32 | 29 | 38 | 34 | 46 | 41 | 51 | 43 |
10 | 43 | 39 | 52 | 46 | 63 | 57 | 70 | 60 |
16 | 57 | 52 | 69 | 62 | 85 | 76 | 94 | 80 |
25 | 75 | 68 | 90 | 80 | 112 | 96 | 119 | 101 |
35 | 92 | 83 | 111 | 99 | 138 | 119 | 148 | 126 |
50 | 110 | 99 | 133 | 118 | 168 | 144 | 180 | 153 |
70 | 139 | 125 | 168 | 149 | 2134 | 184 | 232 | 196 |
95 | 167 | 150 | 201 | 179 | 258 | 223 | 282 | 238 |
120 | 192 | 172 | 232 | 206 | 299 | 259 | 328 | 276 |
150 | 219 | 196 | 258 | 225 | 344 | 299 | 379 | 319 |
185 | 248 | 223 | 294 | 255 | 392 | 341 | 434 | 364 |
240 | 291 | 261 | 344 | 297 | 461 | 403 | 514 | 430 |
300 | 334 | 298 | 394 | 339 | 530 | 464 | 593 | 497 |
400 | – | – | 470 | 402 | 634 | 557 | 715 | 597 |
Table 4D3A PVC Insulation / Copper / Single-core / Armoured - IEE
- Standard: BS 7671
- Table 4D3A
- Single-core armoured 70 °C thermoplastic insulated cables
- Copper conductors
- Conductor temperature: 70 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Reference Method C (clipped direct) | Reference Method F (in free air or in perforated cable tray horizontal or vertical) | ||||||||||
Touching | Touching | Spaced by one cable diameter | |||||||||
2 cables, single- phase AC or DC flat | 3 or 4 cables, three- phase AC flat | 2 cables, single- phase AC or DC flat | 3 cables, three- phase AC flat | 3 cables, three- phase AC trefoil | 2 cables DC | 2 cables AC single-phase AC | 3 or 4 cables three-phase AC | ||||
Horizontal | Vertical | Horizontal | Vertical | Horizontal | Vertical | ||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
50 | 193 | 179 | 205 | 189 | 181 | 229 | 216 | 229 | 217 | 230 | 212 |
70 | 245 | 225 | 259 | 238 | 231 | 294 | 279 | 287 | 272 | 286 | 263 |
95 | 296 | 269 | 313 | 285 | 280 | 357 | 340 | 349 | 332 | 338 | 313 |
120 | 342 | 309 | 360 | 327 | 324 | 415 | 396 | 401 | 383 | 385 | 357 |
150 | 393 | 352 | 413 | 373 | 373 | 479 | 458 | 449 | 429 | 436 | 405 |
185 | 447 | 399 | 469 | 422 | 425 | 548 | 525 | 511 | 489 | 490 | 456 |
240 | 525 | 465 | 550 | 492 | 501 | 648 | 622 | 593 | 568 | 566 | 528 |
300 | 594 | 515 | 624 | 547 | 567 | 748 | 719 | 668 | 640 | 616 | 578 |
400 | 687 | 575 | 723 | 618 | 657 | 885 | 851 | 737 | 707 | 674 | 632 |
500 | 763 | 622 | 805 | 673 | 731 | 1035 | 997 | 810 | 777 | 721 | 676 |
630 | 843 | 669 | 891 | 728 | 809 | 1218 | 1174 | 893 | 856 | 771 | 723 |
800 | 919 | 710 | 976 | 777 | 886 | 1441 | 1390 | 943 | 905 | 824 | 772 |
1000 | 975 | 737 | 1041 | 808 | 945 | 1685 | 1627 | 1008 | 967 | 872 | 816 |
Table 4D4A PVC Insulation / Copper / Multi-core / Armoured - IEE
- Standard: BS 7671
- Table 4D4A
- Multi-core armoured 70 °C thermoplastic insulated cables
- Copper conductors
- Conductor temperature: 70 °C
- Air Ambient temperature: 30 °C
- Ground Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | |||||
---|---|---|---|---|---|---|
Reference Method C (Clipped direct) | Reference Method E (in free air or in perforated cable tray horizontal or vertical) | Reference Method F (direct in ground or in ducting in ground, in or around buildings) | ||||
1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | |
1 | 2 | 3 | 4 | 5 | 6 | 7 |
1.5 | 21 | 18 | 22 | 19 | 22 | 18 |
2.5 | 28 | 25 | 31 | 26 | 29 | 24 |
4 | 38 | 33 | 41 | 35 | 37 | 30 |
6 | 49 | 42 | 53 | 45 | 46 | 38 |
10 | 67 | 58 | 72 | 62 | 60 | 507 |
16 | 89 | 77 | 97 | 83 | 78 | 64 |
25 | 118 | 102 | 128 | 110 | 99 | 82 |
35 | 145 | 125 | 157 | 135 | 119 | 98 |
50 | 175 | 151 | 190 | 163 | 140 | 116 |
70 | 222 | 192 | 241 | 207 | 173 | 143 |
95 | 269 | 231 | 291 | 251 | 204 | 169 |
120 | 310 | 267 | 336 | 290 | 231 | 192 |
150 | 356 | 306 | 386 | 332 | 261 | 217 |
185 | 405 | 348 | 439 | 378 | 292 | 243 |
240 | 476 | 409 | 516 | 445 | 336 | 280 |
300 | 547 | 469 | 592 | 510 | 379 | 316 |
400 | 621 | 540 | 683 | 590 | – | – |
Table 4E1A XLPE Insulation / Copper / Single-core / Non-armoured - IEE
- Standard: BS 7671
- Table 4E1A
- Single-core 90 °C thermosetting insulated cables, non armoured, with or without sheath
- Copper conductors
- Conductor temperature: 90 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Reference Method A (enclosed in conduit in thermally insulated wall etc.) | Reference Method B (enclosed in conduit on a wall or in trunking etc.) | Reference Method C (Clipped direct) | Reference Method F (in free air or in perforated cable tray horizontal or vertical) | ||||||||
Touching | Spaced by one diameter | ||||||||||
2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC flat | 3 cables, three- phase AC flat | 3 cables, three- phase AC trefoil | 2 cables single-phase AC or DC or 3 cables three-phase AC flat | ||
Horizontal | Vertical | ||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
1 | 14 | 13 | 17 | 15 | 19 | 17.5 | – | – | – | – | – |
1.5 | 19 | 17 | 23 | 20 | 25 | 23 | – | – | – | – | – |
2.5 | 26 | 23 | 31 | 28 | 34 | 31 | – | – | – | – | – |
4 | 35 | 31 | 42 | 37 | 46 | 41 | – | – | – | – | – |
6 | 45 | 40 | 54 | 48 | 59 | 54 | – | – | – | – | – |
10 | 61 | 54 | 75 | 66 | 81 | 74 | – | – | – | – | – |
16 | 81 | 73 | 100 | 88 | 109 | 99 | – | – | – | – | – |
25 | 106 | 95 | 133 | 117 | 143 | 130 | 161 | 141 | 135 | 182 | 161 |
35 | 131 | 117 | 164 | 144 | 176 | 161 | 200 | 176 | 169 | 226 | 201 |
50 | 158 | 141 | 198 | 175 | 228 | 209 | 242 | 216 | 207 | 275 | 246 |
70 | 200 | 179 | 253 | 222 | 293 | 268 | 310 | 279 | 268 | 353 | 318 |
95 | 241 | 216 | 306 | 269 | 355 | 326 | 377 | 342 | 328 | 430 | 389 |
120 | 278 | 249 | 354 | 312 | 413 | 379 | 437 | 400 | 383 | 500 | 454 |
150 | 318 | 285 | 393 | 342 | 476 | 436 | 504 | 464 | 444 | 577 | 527 |
185 | 362 | 324 | 449 | 384 | 545 | 500 | 575 | 533 | 510 | 661 | 605 |
240 | 424 | 380 | 528 | 450 | 644 | 590 | 679 | 634 | 607 | 781 | 719 |
300 | 486 | 435 | 603 | 514 | 743 | 681 | 783 | 736 | 703 | 902 | 833 |
400 | – | – | 683 | 584 | 868 | 793 | 940 | 868 | 823 | 1085 | 1008 |
500 | – | – | 783 | 666 | 990 | 904 | 1083 | 998 | 946 | 1253 | 1169 |
630 | – | – | 900 | 764 | 1130 | 1033 | 1254 | 1151 | 1088 | 1454 | 1362 |
800 | – | – | – | – | 1288 | 1179 | 1358 | 1275 | 1214 | 1581 | 1485 |
1000 | – | – | – | – | 1443 | 1323 | 1520 | 1436 | 1349 | 1775 | 1671 |
Table 4E2A XLPE Insulation / Copper / Multi-core / Non-armoured - IEE
- Standard: BS 7671
- Table 4E2A
- Multi-core 90 °C thermosetting insulated and thermoplastic sheathed cables, non armoured
- Copper conductors
- Conductor temperature: 90 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | |||||||
---|---|---|---|---|---|---|---|---|
Reference Method A (enclosed in conduit in thermally insulated wall etc.) | Reference Method B (enclosed in conduit on a wall or in trunking etc.) | Reference Method C (Clipped direct) | Reference Method E (in free air or in perforated cable tray horizontal or vertical) | |||||
1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
1 | 14.5 | 13 | 17 | 15 | 19 | 17 | 21 | 18 |
1.5 | 18.5 | 16.5 | 22 | 19.5 | 24 | 22 | 26 | 23 |
2.5 | 25 | 22 | 30 | 26 | 33 | 30 | 36 | 32 |
4 | 33 | 30 | 40 | 35 | 45 | 40 | 49 | 42 |
6 | 42 | 38 | 51 | 44 | 58 | 52 | 63 | 54 |
10 | 57 | 51 | 69 | 60 | 80 | 71 | 86 | 75 |
16 | 76 | 68 | 91 | 80 | 107 | 96 | 115 | 100 |
25 | 99 | 89 | 119 | 105 | 138 | 119 | 149 | 127 |
35 | 121 | 109 | 146 | 128 | 171 | 147 | 185 | 158 |
50 | 145 | 130 | 175 | 154 | 209 | 179 | 225 | 192 |
70 | 183 | 164 | 221 | 194 | 269 | 229 | 289 | 246 |
95 | 220 | 197 | 265 | 233 | 328 | 278 | 352 | 298 |
120 | 253 | 227 | 305 | 268 | 382 | 322 | 410 | 346 |
150 | 290 | 259 | 334 | 300 | 441 | 371 | 473 | 399 |
185 | 329 | 295 | 384 | 340 | 506 | 424 | 542 | 456 |
240 | 386 | 346 | 459 | 398 | 599 | 500 | 641 | 538 |
300 | 442 | 396 | 532 | 455 | 693 | 576 | 741 | 621 |
400 | – | – | 625 | 536 | 803 | 667 | 865 | 741 |
Table 4E3A XLPE Insulation / Copper / Single-core / Armoured - IEE
- Standard: BS 7671
- Table 4E3A
- Single-core armoured 90 °C thermosetting insulated cables
- Copper conductors
- Conductor temperature: 90 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Reference Method C (clipped direct) | Reference Method F (in free air or in perforated cable tray horizontal or vertical) | ||||||||||
Touching | Touching | Spaced by one cable diameter | |||||||||
2 cables, single- phase AC or DC flat | 3 or 4 cables, three- phase AC flat | 2 cables, single- phase AC or DC flat | 3 cables, three- phase AC flat | 3 cables, three- phase AC trefoil | 2 cables DC | 2 cables AC single-phase AC | 3 or 4 cables three-phase AC | ||||
Horizontal | Vertical | Horizontal | Vertical | Horizontal | Vertical | ||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
50 | 237 | 220 | 253 | 232 | 222 | 284 | 270 | 282 | 266 | 288 | 266 |
70 | 303 | 277 | 322 | 293 | 285 | 356 | 349 | 357 | 337 | 358 | 331 |
95 | 367 | 333 | 389 | 352 | 246 | 446 | 426 | 436 | 412 | 425 | 393 |
120 | 425 | 383 | 449 | 405 | 402 | 519 | 497 | 504 | 477 | 485 | 449 |
150 | 488 | 437 | 516 | 462 | 463 | 600 | 575 | 566 | 539 | 549 | 510 |
185 | 557 | 496 | 587 | 524 | 529 | 688 | 660 | 643 | 614 | 618 | 574 |
240 | 656 | 579 | 689 | 612 | 625 | 815 | 782 | 749 | 714 | 715 | 666 |
300 | 755 | 662 | 792 | 700 | 720 | 943 | 906 | 842 | 805 | 810 | 755 |
400 | 853 | 717 | 899 | 767 | 815 | 1137 | 1094 | 929 | 889 | 848 | 797 |
500 | 962 | 791 | 1016 | 851 | 918 | 1314 | 1266 | 1032 | 989 | 923 | 871 |
630 | 1082 | 861 | 1146 | 935 | 1027 | 1528 | 1474 | 1139 | 1092 | 992 | 940 |
800 | 1170 | 904 | 1246 | 987 | 1119 | 1809 | 1744 | 1204 | 1155 | 1042 | 978 |
1000 | 1261 | 961 | 1345 | 1055 | 1214 | 2100 | 2026 | 1289 | 1238 | 1110 | 1041 |
Table 4E4A XLPE Insulation / Copper / Multi-core / Armoured - IEE
- Standard: BS 7671
- Table 4E4A
- Multi-core armoured 90 °C thermosetting insulated cables
- Copper conductors
- Conductor temperature: 90 °C
- Air Ambient temperature: 30 °C
- Ground Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | |||||
---|---|---|---|---|---|---|
Reference Method C (Clipped direct) | Reference Method E (in free air or in perforated cable tray horizontal or vertical) | Reference Method F (direct in ground or in ducting in ground, in or around buildings) | ||||
1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | |
1 | 2 | 3 | 4 | 5 | 6 | 7 |
1.5 | 27 | 23 | 29 | 25 | 25 | 21 |
2.5 | 36 | 31 | 39 | 33 | 33 | 28 |
4 | 49 | 42 | 52 | 44 | 43 | 36 |
6 | 62 | 53 | 66 | 56 | 53 | 44 |
10 | 85 | 73 | 90 | 78 | 71 | 58 |
16 | 110 | 94 | 115 | 99 | 91 | 75 |
25 | 146 | 124 | 152 | 131 | 116 | 96 |
35 | 180 | 154 | 188 | 162 | 139 | 115 |
50 | 219 | 187 | 228 | 197 | 164 | 135 |
70 | 279 | 238 | 291 | 251 | 203 | 167 |
95 | 338 | 289 | 354 | 304 | 239 | 197 |
120 | 392 | 335 | 410 | 353 | 271 | 223 |
150 | 451 | 386 | 472 | 406 | 306 | 251 |
185 | 515 | 441 | 539 | 463 | 343 | 281 |
300 | 698 | 599 | 732 | 628 | 446 | 365 |
400 | 787 | 673 | 847 | 728 | – | – |
Table 4H1A PVC Insulation / Aluminium / Single-core / Non-armoured - IEE
- Standard: BS 7671
- Table 4H1A
- Single-core 70 °C thermoplastic insulated cables, non armoured, with or without sheath
- Aluminium conductors
- Conductor temperature: 70 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Reference Method A (enclosed in conduit in thermally insulated wall etc.) | Reference Method B (enclosed in conduit on a wall or in trunking etc.) | Reference Method C (Clipped direct) | Reference Method F (in free air or in perforated cable tray horizontal or vertical) | ||||||||
Touching | Spaced by one diameter | ||||||||||
2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC flat | 3 cables, three- phase AC flat | 3 cables, three- phase AC trefoil | 2 cables single-phase AC or DC or 3 cables three-phase AC flat | ||
Horizontal | Vertical | ||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
50 | 93 | 84 | 118 | 104 | 125 | 110 | 149 | 133 | 128 | 169 | 152 |
70 | 118 | 107 | 150 | 133 | 160 | 140 | 192 | 173 | 166 | 217 | 196 |
95 | 142 | 129 | 181 | 161 | 195 | 170 | 235 | 212 | 203 | 265 | 241 |
120 | 164 | 149 | 210 | 186 | 226 | 197 | 273 | 247 | 237 | 308 | 282 |
150 | 189 | 170 | 234 | 204 | 261 | 227 | 316 | 287 | 274 | 356 | 327 |
185 | 215 | 194 | 266 | 230 | 298 | 259 | 363 | 330 | 316 | 407 | 376 |
240 | 252 | 227 | 312 | 269 | 352 | 305 | 430 | 392 | 375 | 482 | 447 |
300 | 289 | 261 | 358 | 306 | 406 | 351 | 497 | 455 | 434 | 557 | 519 |
380 | – | – | 413 | 352 | 511 | 472 | 543 | 502 | 507 | 625 | 584 |
480 | – | – | 477 | 405 | 591 | 546 | 629 | 582 | 590 | 726 | 680 |
600 | – | – | 545 | 462 | 679 | 626 | 722 | 669 | 680 | 837 | 787 |
740 | – | – | – | – | 771 | 709 | 820 | 761 | 776 | 956 | 902 |
960 | – | – | – | – | 900 | 823 | 953 | 886 | 907 | 1125 | 1066 |
1200 | – | – | – | – | 1022 | 926 | 1073 | 999 | 1026 | 1293 | 1229 |
Table 4H2A PVC Insulation / Aluminium / Multi-core / Non-armoured - IEE
- Standard: BS 7671
- Table 4H2A
- Multi-core 70 °C thermoplastic insulated and thermoplastic sheathed cables, non armoured
- Aluminium conductors
- Conductor temperature: 70 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | |||||||
---|---|---|---|---|---|---|---|---|
Reference Method A (enclosed in conduit in thermally insulated wall etc.) | Reference Method B (enclosed in conduit on a wall or in trunking etc.) | Reference Method C (Clipped direct) | Reference Method E (in free air or in perforated cable tray horizontal or vertical) | |||||
1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
16 | 44 | 41 | 54 | 48 | 66 | 59 | 73 | 61 |
25 | 58 | 53 | 71 | 62 | 83 | 73 | 89 | 78 |
35 | 71 | 65 | 86 | 77 | 103 | 90 | 111 | 96 |
50 | 86 | 78 | 104 | 92 | 125 | 110 | 135 | 117 |
70 | 108 | 98 | 131 | 116 | 160 | 140 | 173 | 150 |
95 | 130 | 118 | 157 | 139 | 195 | 170 | 210 | 183 |
120 | – | 135 | – | 160 | – | 197 | – | 212 |
150 | – | 155 | – | 176 | – | 227 | – | 245 |
185 | – | 176 | – | 199 | – | 259 | 280 | |
240 | – | 207 | – | 232 | – | 305 | – | 330 |
300 | – | 237 | – | 265 | – | 351 | – | 381 |
Table 4H3A PVC Insulation / Aluminium / Single-core / Armoured - IEE
- Standard: BS 7671
- Table 4H3A
- Single-core armoured 70 °C thermoplastic insulated cables
- Aluminium conductors
- Conductor temperature: 70 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Reference Method C (clipped direct) | Reference Method F (in free air or in perforated cable tray horizontal or vertical) | ||||||||||
Touching | Touching | Spaced by one cable diameter | |||||||||
2 cables, single- phase AC or DC flat | 3 or 4 cables, three- phase AC flat | 2 cables, single- phase AC or DC flat | 3 cables, three- phase AC flat | 3 cables, three- phase AC trefoil | 2 cables DC | 2 cables AC single-phase AC | 3 or 4 cables three-phase AC | ||||
Horizontal | Vertical | Horizontal | Vertical | Horizontal | Vertical | ||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
50 | 143 | 133 | 152 | 141 | 131 | 167 | 157 | 168 | 159 | 169 | 155 |
70 | 183 | 168 | 194 | 178 | 168 | 214 | 202 | 212 | 200 | 213 | 196 |
95 | 221 | 202 | 234 | 214 | 205 | 261 | 247 | 259 | 245 | 255 | 236 |
120 | 255 | 233 | 270 | 246 | 238 | 303 | 288 | 299 | 285 | 293 | 272 |
150 | 294 | 267 | 310 | 282 | 275 | 349 | 333 | 340 | 323 | 335 | 312 |
185 | 334 | 303 | 352 | 319 | 315 | 400 | 382 | 389 | 371 | 379 | 354 |
240 | 393 | 354 | 413 | 374 | 372 | 472 | 452 | 457 | 437 | 443 | 415 |
300 | 452 | 405 | 474 | 427 | 430 | 545 | 523 | 520 | 498 | 505 | 475 |
380 | 518 | 452 | 543 | 479 | 497 | 638 | 613 | 583 | 559 | 551 | 518 |
480 | 586 | 501 | 616 | 534 | 568 | 742 | 715 | 655 | 629 | 604 | 568 |
600 | 658 | 550 | 692 | 589 | 642 | 859 | 828 | 724 | 696 | 656 | 618 |
740 | 728 | 596 | 769 | 642 | 715 | 986 | 952 | 802 | 770 | 707 | 666 |
960 | 819 | 651 | 868 | 706 | 808 | 1171 | 1133 | 866 | 832 | 770 | 726 |
1200 | 893 | 692 | 952 | 756 | 880 | 1360 | 1317 | 938 | 902 | 822 | 774 |
Table 4H4A PVC Insulation / Aluminium / Multi-core / Armoured - IEE
- Standard: BS 7671
- Table 4H4A
- Multi-core armoured 70 °C thermoplastic insulated cables
- Aluminium conductors
- Conductor temperature: 70 °C
- Air Ambient temperature: 30 °C
- Ground Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | |||||
---|---|---|---|---|---|---|
Reference Method C (Clipped direct) | Reference Method E (in free air or in perforated cable tray horizontal or vertical) | Reference Method F (direct in ground or in ducting in ground, in or around buildings) | ||||
1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | |
1 | 2 | 3 | 4 | 5 | 6 | 7 |
16 | 68 | 58 | 71 | 61 | – | – |
25 | 89 | 76 | 94 | 80 | 77 | 64 |
35 | 109 | 94 | 115 | 99 | 93 | 77 |
50 | 131 | 113 | 139 | 119 | 109 | 91 |
70 | 165 | 143 | 175 | 151 | 135 | 112 |
95 | 199 | 174 | 211 | 186 | 159 | 132 |
120 | – | 202 | – | 216 | – | 1502 |
150 | – | 232 | – | 250 | – | 169 |
185 | – | 265 | – | 287 | – | 190 |
240 | – | 312 | – | 342 | – | 218 |
300 | – | 360 | – | 399 | – | 247 |
Table 4J1A XLPE Insulation / Aluminium / Single-core / Non-armoured - IEE
- Standard:BS 7671
- Table 4J1A
- Single-core 90 °C thermosetting insulated cables, non armoured, with or without sheath
- Aluminium conductors
- Conductor temperature: 90 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Reference Method A (enclosed in conduit in thermally insulated wall etc.) | Reference Method B (enclosed in conduit on a wall or in trunking etc.) | Reference Method C (Clipped direct) | Reference Method F (in free air or in perforated cable tray horizontal or vertical) | ||||||||
Touching | Spaced by one diameter | ||||||||||
2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC | 3 or 4 cables, three- phase AC | 2 cables, single- phase AC or DC flat | 3 cables, three- phase AC flat | 3 cables, three- phase AC trefoil | 2 cables single-phase AC or DC or 3 cables three-phase AC flat | ||
Horizontal | Vertical | ||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
50 | 125 | 113 | 157 | 140 | 154 | 136 | 184 | 165 | 159 | 210 | 188 |
70 | 158 | 142 | 200 | 179 | 198 | 174 | 237 | 215 | 206 | 271 | 244 |
95 | 191 | 171 | 242 | 217 | 242 | 211 | 289 | 264 | 253 | 332 | 300 |
120 | 220 | 197 | 281 | 251 | 280 | 245 | 337 | 308 | 296 | 387 | 351 |
150 | 253 | 226 | 307 | 267 | 324 | 283 | 389 | 358 | 343 | 448 | 408 |
185 | 288 | 256 | 351 | 300 | 371 | 323 | 447 | 413 | 395 | 515 | 470 |
240 | 338 | 300 | 412 | 351 | 439 | 382 | 530 | 492 | 471 | 611 | 561 |
300 | 387 | 344 | 471 | 402 | 508 | 440 | 613 | 571 | 544 | 708 | 652 |
380 | – | – | – | – | 658 | 594 | 679 | 628 | 638 | 798 | 742 |
480 | – | – | – | – | 765 | 692 | 786 | 728 | 743 | 927 | 865 |
600 | – | – | – | – | 871 | 791 | 903 | 836 | 849 | 1058 | 990 |
740 | – | – | – | – | 1001 | 911 | 1025 | 951 | 979 | 1218 | 1143 |
960 | – | – | – | – | 1176 | 1072 | 1191 | 1108 | 1151 | 1440 | 1355 |
1200 | – | – | – | – | 1333 | 1217 | 1341 | 1249 | 1307 | 1643 | 1550 |
Table 4J2A XLPE Insulation / Aluminium / Multi-core / Non-armoured - IEE
- Standard: BS 7671
- Table 4J2A
- Multi-core 90 °C thermosetting insulated and thermoplastic sheathed cables, non armoured
- Aluminium conductors
- Conductor temperature: 90 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | |||||||
---|---|---|---|---|---|---|---|---|
Reference Method A (enclosed in conduit in thermally insulated wall etc.) | Reference Method B (enclosed in conduit on a wall or in trunking etc.) | Reference Method C (Clipped direct) | Reference Method E (in free air or in perforated cable tray horizontal or vertical) | |||||
1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
16 | 60 | 55 | 72 | 64 | 84 | 76 | 91 | 77 |
25 | 78 | 71 | 94 | 84 | 101 | 90 | 108 | 97 |
35 | 96 | 87 | 115 | 103 | 126 | 112 | 135 | 120 |
50 | 115 | 104 | 138 | 124 | 154 | 136 | 164 | 146 |
70 | 145 | 131 | 175 | 156 | 198 | 174 | 211 | 187 |
95 | 175 | 157 | 210 | 188 | 241 | 211 | 257 | 227 |
120 | – | 180 | – | 216 | – | 245 | – | 263 |
150 | – | 206 | – | 240 | – | 283 | – | 304 |
185 | – | 233 | – | 272 | – | 323 | – | 347 |
240 | – | 273 | – | 318 | – | 382 | – | 409 |
300 | – | 313 | – | 364 | – | 440 | – | 471 |
Table 4J3A XLPE Insulation / Aluminium / Single-core / Armoured - IEE
- Standard: BS 7671
- Table 4J3A
- Single-core armoured 90 °C thermosetting insulated cables
- Aluminium conductors
- Conductor temperature: 90 °C
- Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Reference Method C (clipped direct) | Reference Method F (in free air or in perforated cable tray horizontal or vertical) | ||||||||||
Touching | Touching | Spaced by one cable diameter | |||||||||
2 cables, single- phase AC or DC flat | 3 or 4 cables, three- phase AC flat | 2 cables, single- phase AC or DC flat | 3 cables, three- phase AC flat | 3 cables, three- phase AC trefoil | 2 cables DC | 2 cables AC single-phase AC | 3 or 4 cables three-phase AC | ||||
Horizontal | Vertical | Horizontal | Vertical | Horizontal | Vertical | ||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
50 | 179 | 165 | 192 | 176 | 162 | 216 | 197 | 212 | 199 | 215 | 192 |
70 | 228 | 209 | 244 | 222 | 207 | 275 | 253 | 269 | 254 | 270 | 244 |
95 | 276 | 252 | 294 | 267 | 252 | 332 | 307 | 328 | 310 | 324 | 296 |
120 | 320 | 291 | 340 | 308 | 292 | 384 | 357 | 378 | 358 | 372 | 343 |
150 | 368 | 333 | 390 | 352 | 337 | 441 | 411 | 429 | 409 | 424 | 394 |
185 | 419 | 378 | 444 | 400 | 391 | 511 | 480 | 490 | 467 | 477 | 447 |
240 | 494 | 443 | 521 | 468 | 465 | 605 | 572 | 576 | 549 | 554 | 523 |
300 | 568 | 508 | 597 | 536 | 540 | 701 | 666 | 654 | 624 | 626 | 595 |
380 | 655 | 573 | 688 | 608 | 625 | 812 | 780 | 735 | 704 | 693 | 649 |
480 | 747 | 642 | 786 | 685 | 714 | 942 | 906 | 825 | 790 | 765 | 717 |
600 | 836 | 706 | 880 | 757 | 801 | 1076 | 1036 | 909 | 872 | 832 | 780 |
740 | 934 | 764 | 988 | 824 | 897 | 1250 | 1205 | 1204 | 989 | 890 | 835 |
960 | 1056 | 838 | 1121 | 911 | 1014 | 1488 | 1435 | 1094 | 1052 | 970 | 911 |
1200 | 1163 | 903 | 1236 | 990 | 1118 | 1715 | 1658 | 1187 | 1141 | 1043 | 980 |
Table 4J4A XLPE Insulation / Aluminium / Multi-core / Armoured - IEE
- Standard: BS 7671
- Table 4J4A
- Multi-core armoured 90 °C thermosetting insulated cables
- Aluminium conductors
- Conductor temperature: 90 °C
- Air Ambient temperature: 30 °C
- Ground Ambient temperature: 30 °C
Conductor nominal cross- sectional area [mm²] | Current-carrying capacities in [A] | |||||
---|---|---|---|---|---|---|
Reference Method C (Clipped direct) | Reference Method E (in free air or in perforated cable tray horizontal or vertical) | Reference Method F (direct in ground or in ducting in ground, in or around buildings) | ||||
1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | 1 two-core cable,single-phase AC or DC | 1 three-core cable or 1 four-core cable three-phase AC | |
1 | 2 | 3 | 4 | 5 | 6 | 7 |
16 | 82 | 71 | 85 | 74 | 71 | 59 |
25 | 108 | 92 | 112 | 98 | 90 | 75 |
35 | 132 | 113 | 138 | 120 | 108 | 90 |
50 | 159 | 137 | 166 | 145 | 128 | 106 |
70 | 201 | 174 | 211 | 185 | 158 | 130 |
95 | 242 | 214 | 254 | 224 | 186 | 154 |
120 | – | 249 | – | 264 | – | 174 |
150 | – | 284 | – | 305 | – | 197 |
185 | – | 328 | – | 350 | – | 220 |
240 | – | 386 | – | 418 | – | 253 |
300 | – | 441 | – | 488 | – | 286 |