Instrumentation cables - NBR 10300

Individual shielded instrumentation cables - BFI (Copper / Steel Tape - Copper / Steel Mesh)

    INNOVCABLE INSTRUMENTATION CABLE BFI 300V NBR 10300

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 2 NBR NM 280 stranding.
    2) Thermoplastic compound insulation
    based on polyvinyl chloride (PVC/A).
    3) Conductors are assembled in pairs, suits or squares.
    4) Pitch of torsion: 50 to 65mm.
    5) Individual shielding in aluminized polyester tape, with flexible drain conductor of section 0,5 mm², formed by tinned electrolytic copper wires.
    6) Separator in polyester tape.
    7) Communication cable formed by a stranded conductor of section 0,50mm² with isolation in (PVC/A) blue colour (when applied).
    8) Thermoplastic compound covering based on polyvinyl chloride (PVC/ST1) in black colour.

    - Insulation voltage: 300V

    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Alternating current electric tension
    Insulation resistance.

    THIS PRODUCT'S DIFFERENTIALS.
    - 100% virgin copper
    - 100% electrolytic copper - 99.90% minimum pure (* including silver)
    - High flexibility class 5 (when requested)
    - Bright colours
    - Lower dielectric loss
    - Lower ohmic resistance
    - Anti-flame
    - 100% National
    - Attend Hart ® protocol (4 - 20mA), digital and point to point instrumentation

    Identification

    The pairs are made in Black and White, and the suits in Black, White and Red.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280
    ABNT/MERCOSUL: NM-IEC 60228
    NBR NM IEC 60332-3-23, category B
    ABNT: NBR 10300 (pairs, tents and courts)
    NBR 6812
    NBR 6251

    Applications

    They are used in fixed installations, for conducting analog (4 - 20mA) and digital signals, point-to-point instrumentation, Hart ® protocol, connections of various sensors and meters, power supply to conventional and electronic relays, in industrial environments in general.
    The BFI Instrumentation cables have individual shielding and are recommended for cases in which excellent levels of protection against external electromagnetic interference are required, and maximum immunity against the emergence of "crosstalk" (crosstalk) between the various pairs/pairs, providing electrical discharge of the same.
    Excellent flexibility, resistance to chemicals, humidity and UV rays, anti-flame and self-extinguishing, complying with vertical flame spread tests, according to NBR NM IEC 60332-3-23, category B.

    Maximum Conductor Temperature

    IN CONTINUOUS REGIME: 70ºC (PVC/A)

    Notes

    The BFI INSTRUMENTATION CABLE can be manufactured in another section, dimensional or material at the customer's request. Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 5 stranding.
    2- Different sections and number of veins.
    3- Insulation material of the veins / other temperatures:
    PVC/E -105 ºC
    XLPE - 125 ºC or 90 ºC
    HEPR - 90 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    LSZH (non-halogenated polyolefin compound)
    5- Perfectly cylindrical cover for cable gland applications in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE INSTRUMENTATION CABLE BFI FC 300V NBR 10300

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 2 NBR NM 280 stranding.
    2) Thermoplastic compound insulation
    based on polyvinyl chloride (PVC/A).
    3) Conductors are assembled in pairs, suits or squares.
    4) Pitch of torsion: 50 to 65mm
    5) Individual shielding in aluminized polyester tape, with flexible drain conductor of 0,5 mm² section, formed by tinned electrolytic copper wires.
    6) Separator in polyester tape.
    7) Communication cable formed by a stranded conductor of section 0,50mm² with isolation in (PVC/A) blue colour (when applied).
    8) Intermediate layer in thermoplastic compound based on polyvinyl chloride (PVC/ST1).
    9) Shielding in copper tape.
    10) Cover in thermoplastic compound based on polyvinyl chloride (PVC/ST1) in black colour.

    - Insulation voltage: 300V

    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Alternating current electric tension
    Insulation resistance.

    THIS PRODUCT'S DIFFERENTIALS.
    - 100% virgin copper
    - 100% electrolytic copper - 99.90% minimum pure (* including silver)
    - High flexibility class 5 (when requested)
    - Bright colours
    - Lower dielectric loss
    - Lower ohmic resistance
    - Anti-flame
    - 100% National
    - Attend Hart ® protocol (4 - 20mA), digital and point to point instrumentation

    Identification

    The pairs are made in Black and White, and the suits in Black, White and Red.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280
    ABNT/MERCOSUL: NM-IEC 60228
    NBR NM IEC 60332-3-23, category B
    ABNT: NBR 10300 (pairs, tents and courts)
    NBR 6812
    NBR 6251

    Applications

    They are used in fixed installations, conducting analog (4 - 20mA) and digital signals, point-to-point instrumentation, Hart ® protocol, connections of various sensors and meters, power supply to conventional and electronic relays, in industrial environments in general.
    The BFI FC instrumentation cables have individual aluminised polyester tape shielding and copper tape shielding and are recommended for cases in which excellent levels of protection against external electromagnetic interference are required, and maximum immunity against the emergence of crosstalk (crosstalk) between the various pairs/pairs, providing electrical discharge of the same.
    Excellent flexibility, resistance to chemicals, humidity and UV rays, anti-flame and self-extinguishing, complying with vertical flame spread tests, according to NBR NM IEC 60332-3-23, category B.

    Maximum Conductor Temperature

    IN CONTINUOUS REGIME: 70ºC (PVC/A)

    Notes

    The BFI FC INSTRUMENTATION CABLE can be manufactured in another section, dimensional or material at the customer's request. Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 5 stranding.
    2- Different sections and number of veins.
    3- Insulation material of the veins / other temperatures:
    PVC/E -105 ºC
    XLPE - 125 ºC or 90 ºC
    HEPR - 90 ºC
    PE - 80 ºC
    4- Material of the intermediate layer and the cover:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    LSZH (non-halogenated polyolefin compound)
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex)

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE INSTRUMENTATION CABLE BFI FA 300V NBR 10300

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 2 NBR NM 280 stranding.
    2) Insulation in thermoplastic compound based on
    based on polyvinyl chloride (PVC/A).
    3) Conductors in pairs, suits or blocks.
    4) Pitch of torsion: 50 to 65mm
    5) Individual shielding in aluminized polyester tape, with flexible drain conductor of section 0,5 mm², formed by tinned electrolytic copper wires.
    6) Separator in polyester tape.
    7) Communication cable formed by a stranded conductor of section 0,50mm² with isolation in (PVC/A) blue colour (when applied).
    8) Intermediate layer in thermoplastic compound based on polyvinyl chloride (PVC/ST1).
    9) Shielding in galvanized steel tape.
    10) Cover in thermoplastic compound based on polyvinyl chloride (PVC/ST1).

    - Insulation voltage: 300V

    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Alternating current electric tension
    Insulation resistance.

    THIS PRODUCT'S DIFFERENTIALS.
    - 100% virgin copper
    - 100% electrolytic copper - 99.90% minimum pure (* including silver)
    - High flexibility class 5 (when requested)
    - Bright colours
    - Lower dielectric loss
    - Lower ohmic resistance
    - Anti-flame
    - 100% National
    - Attend Hart ® protocol (4 - 20mA), digital and point to point instrumentation

    Identification

    The pairs are made in Black and White, and the suits in Black, White and Red.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280
    ABNT/MERCOSUL: NM-IEC 60228
    NBR NM IEC 60332-3-23, category B
    ABNT: NBR 10300 (pairs, tents and courts)
    NBR 6812
    NBR 6251

    Applications

    They are used in fixed installations, conducting analog (4 - 20mA) and digital signals, point-to-point instrumentation, Hart ® protocol, connections of various sensors and meters, power supply to conventional and electronic relays, in industrial environments in general.
    The BFI FA Instrumentation cables have individual shielding in aluminised polyester tape, and are recommended for cases in which excellent levels of protection against external electromagnetic interference are required, and maximum immunity against the emergence of "crosstalk" (crosstalk) between the various pairs/pairs/frames, providing electrical discharge of the same. It has mechanical protection with the application of galvanized steel tape, providing excellent resistance to impacts and other mechanical demands.
    Flexible, resistant to chemicals, humidity and UV rays, anti-flame and self-extinguishing, complying with the vertical flame propagation tests, according to NBR NM IEC 60332-3-23, category B.

    Maximum Conductor Temperature

    IN CONTINUOUS REGIME: 70ºC (PVC/A)

    Notes

    The BFI FA INSTRUMENTATION CABLE can be manufactured in another section, dimensional or material at the customer's request. Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 5 stranding.
    2- Different sections and number of veins.
    3- Insulation material of the veins / other temperatures:
    PVC/E -105 ºC
    XLPE - 125 ºC or 90 ºC
    HEPR - 90 ºC
    PE - 80 ºC
    4- Material of the intermediate layer and the cover:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    LSZH (non-halogenated polyolefin compound)
    5- Perfectly cylindrical cover for cable gland applications in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE INSTRUMENTATION CABLE BFI BTC 300V NBR 10300

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 2 NBR NM 280 stranding.
    2) Thermoplastic compound insulation
    based on polyvinyl chloride (PVC/A).
    3) Conductors in pairs, suits or blocks.
    4) Pitch of torsion: 50 to 65mm
    5) Individual shielding in aluminized polyester tape, with flexible drain conductor of section 0,5 mm², formed by tinned electrolytic copper wires.
    6) Separator in polyester tape.
    7) Communication cable formed by a stranded conductor of section 0,50mm² with isolation in (PVC/A) blue colour (when applied).
    8) Intermediate layer in thermoplastic compound based on polyvinyl chloride (PVC/ST1).
    9) Shielding in bare copper wire mesh.
    10) Cover in thermoplastic compound based on polyvinyl chloride (PVC/ST1).

    - Insulation voltage: 300V

    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Alternating current electric tension
    Insulation resistance.

    THIS PRODUCT'S DIFFERENTIALS.
    - 100% virgin copper
    - 100% electrolytic copper - 99.90% minimum pure (* including silver)
    - High flexibility class 5 (when requested)
    - Bright colours
    - Lower dielectric loss
    - Lower ohmic resistance
    - Anti-flame
    - 100% National
    - Attend Hart ® protocol (4 - 20mA), digital and point to point instrumentation

    Identification

    The pairs are made in Black and White, and the suits in Black, White and Red.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280
    ABNT/MERCOSUL: NM-IEC 60228
    NBR NM IEC 60332-3-23, category B
    ABNT: NBR 10300 (pairs, tents and courts)
    NBR 6812
    NBR 6251

    Applications

    They are used in fixed installations, for conducting analog (4 - 20mA) and digital signals, point-to-point instrumentation, Hart ® protocol, connections of various sensors and meters, power supply to conventional and electronic relays, in industrial environments in general.
    The BFI BTC Instrumentation cables have individual shielding in aluminised polyester tape, and are recommended for cases in which excellent levels of protection against external electromagnetic interference are required, and maximum immunity against the emergence of "crosstalk" (crosstalk) between the various pairs/pairs/frames, providing electrical discharge of the same. It also has bare copper wire shielding, providing greater flexibility. Cable resistant to chemical products, humidity and UV rays, anti-flame and self-extinguishable according to vertical flame propagation tests, according to NBR NM IEC 60332-3-23, category B.

    Maximum Conductor Temperature

    IN CONTINUOUS REGIME: 70ºC (PVC/A)

    Notes

    The BFI BTC INSTRUMENTATION CABLE can be manufactured in another section, dimensional or material at the customer's request. Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 5 stranding.
    2- Different sections and number of veins.
    3- Insulation material of the veins / other temperatures:
    PVC/E -105 ºC
    XLPE - 125 ºC or 90 ºC
    HEPR - 90 ºC
    PE - 80 ºC
    4- Material of the intermediate layer and the cover:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    LSZH (non-halogenated polyolefin compound)
    5- Perfectly cylindrical cover for cable gland applications in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE INSTRUMENTATION CABLE BFI BTA 300V NBR 10300

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 2 NBR NM 280 stranding.
    2) Thermoplastic compound insulation
    based on polyvinyl chloride (PVC/A).
    3) Conductors in pairs, suits or blocks.
    4) Pitch of torsion: 50 to 65mm
    5) Individual shielding in aluminized polyester tape, with flexible drain conductor of section 0,5 mm², formed by tinned electrolytic copper wires.
    6) Separator in polyester tape.
    7) Communication cable formed by a stranded conductor of section 0,50mm² with isolation in (PVC/A) blue colour (when applied).
    8) Intermediate layer in thermoplastic compound based on polyvinyl chloride (PVC/ST1).
    9) Shielding in galvanized steel mesh.
    10) Cover in thermoplastic compound based on polyvinyl chloride (PVC/ST1).

    - Insulation voltage: 300V

    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Alternating current electric tension
    Insulation resistance.

    THIS PRODUCT'S DIFFERENTIALS.
    - 100% virgin copper
    - 100% electrolytic copper - 99.90% minimum pure (* including silver)
    - High flexibility class 5 (when requested)
    - Bright colours
    - Lower dielectric loss
    - Lower ohmic resistance
    - Anti-flame
    - 100% National
    - Attend Hart ® protocol (4 - 20mA), digital and point to point instrumentation

    Identification

    The pairs are made in Black and White, and the suits in Black, White and Red.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280
    ABNT/MERCOSUL: NM-IEC 60228
    NBR NM IEC 60332-3-23, category B
    ABNT: NBR 10300 (pairs, tents and courts)
    NBR 6812
    NBR 6251

    Applications

    They are used in fixed installations, for conducting analog (4 - 20mA) and digital signals, point-to-point instrumentation, Hart ® protocol, connections of various sensors and meters, power supply to conventional and electronic relays, in industrial environments in general.
    The BFI BTA Instrumentation cables have individual shielding in aluminised polyester tape and are recommended for cases in which excellent levels of protection against external electromagnetic interference are required, and maximum immunity against the emergence of "crosstalk" (crosstalk) between the various pairs/pairs/frames, providing electrical discharge of the same. They have mechanical protection with the application of galvanized steel mesh, providing greater flexibility. Cable resistant to chemical products, humidity and UV rays, anti-flame and self-extinguishing complying with the vertical flame propagation tests, according to NBR NM IEC 60332-3-23, category B.

    Maximum Conductor Temperature

    IN CONTINUOUS REGIME: 70ºC (PVC/A)

    Notes

    The BFI BTA INSTRUMENTATION CABLE can be manufactured in another section, dimensional or material at the customer's request. Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 5 stranding.
    2- Different sections and number of veins.
    3- Insulation material of the veins / other temperatures:
    PVC/E -105 ºC
    XLPE - 125 ºC or 90 ºC
    HEPR - 90 ºC
    PE - 80 ºC
    4- Material of the intermediate layer and the cover:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    LSZH (non-halogenated polyolefin compound)
    5- Perfectly cylindrical cover for cable gland applications in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español