Control Cables - NBR 7289 / 7290 / 16442

Control cables - NBR 16442

    INNOVCABLE CONTROL CABLE SB ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Polyester tape separator.
    4) Halogen-free, flame-retardant thermoplastic compound (SHF1) cover in black.

    - Insulation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in Alternate Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Low smoke and non-halogenated control cables for voltages up to 1 kV - Performance requirements

    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others. Due to its
    properties of low emission of smoke and toxic gases and flame retardancy, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases
    They are recommended for installations in places with critical systems and equipment where greater reliability and less risk are required.
    They are applied in fixed systems of conduits (embedded or exposed), ducts, duct banks, trays, electrical ducts, electrical panels, among other applications. This cable has good flexibility, resistance to UV, weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The INNOVCABLE SB ATOX HEPR/SHF1 - NBR 16442 control cables can be manufactured in other sections, dimensions or materials, at the customer's request. Innovcable reserves the right to modify this catalogue without prior notice.

    OTHER CONSTRUCTION OPTIONS:
    We can manufacture on request in other configurations.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to:
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Material of the intermediate layer and the cover:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemical products.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex)

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shield in aluminized polyester tape with tinned copper drain wire.
    4) Cover in thermoplastic compound free of halogen and flame retardant (SHF1) in black colour.

    - Insulation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in Alternate Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Non-halogenated control cables with low smoke emission for voltages up to 1 kV - Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signalling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others. Due to their properties of low emission of smoke and toxic gases and flame retardancy, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases when burning, recommended for installations in places with critical systems and equipment where greater reliability and less risk are required. They have collective protection in aluminized polyester tape against electromagnetic interference.
    They are applied in fixed conduit systems (embedded or exposed), ducts, duct banks, trays, electrical ducts, electrical panels, among other applications. This cable has good flexibility, resistance to UV, bad weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF ATOX HEPR/SHF1 - NBR 16442 control cable can be manufactured in other sections, dimensions or materials at the customer's request. Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF FC ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shield in aluminized polyester tape with tinned copper drain wire.
    4) Intermediate cover in thermoplastic compound free of halogen and flame retardant (SHF1).
    5) Shielding in copper tape.
    6) Non-hygroscopic tape.
    7) Cover in halogen free, flame retardant thermoplastic compound (SHF1) in black colour.

    - Insulation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in Alternate Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Non-halogenated control cables with low smoke emission for voltages up to 1 kV - Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signalling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others. Due to their properties of low emission of smoke and toxic gases and flame retardancy, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases when burning, and are recommended for installation in places with critical systems and equipment where greater reliability and less risk are required.
    They are applied in fixed systems of conduits (embedded or exposed), ducts, duct banks, electro-roof gutters, electrical panels, among other applications. It has collective protection in aluminized polyester tape and copper tape against electromagnetic interference. This cable is resistant to UV, bad weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF FC ATOX HEPR/SHF1 - NBR 16442 control cables can be manufactured in other sections, dimensions or materials, at the customer's request.

    Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF FA ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shield in aluminized polyester tape with tinned copper drain wire.
    4) Intermediate cover in thermoplastic compound free of halogen and flame retardant (SHF1).
    5) Shielding in galvanized steel tape.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free, flame-retardant thermoplastic compound (SHF1) in black.

    - Insulation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in Alternate Current
    Isolation resistance

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Non-halogenated control cables with low smoke emission for voltages up to 1 kV - Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signalling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others. Due to their properties of low emission of smoke and toxic gases and flame retardancy, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases when burning, and are recommended for installation in places with critical systems and equipment where greater reliability and less risk are required.
    They are applied in fixed systems of conduits (embedded or exposed), ducts, duct banks, electro-roof gutters, electrical panels, among other applications. It has collective protection against electromagnetic interference and mechanical protection of galvanized steel tape. This cable has good flexibility, resistance to UV, bad weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF FA ATOX HEPR/SHF1 - NBR 16442 control cables can be manufactured in other sections, dimensions or materials, at the customer's request.

    Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF BTC ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shield in aluminized polyester tape with tinned copper drain wire.
    4) Intermediate cover in thermoplastic compound free of halogen and flame retardant (SHF1).
    5) Shielding in copper braid.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free, flame-retardant thermoplastic compound (SHF1) in black colour.

    - Insulation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in Alternate Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Non-halogenated control cables with low smoke emission for voltages up to 1 kV - Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signalling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others.
    They are applied in fixed systems of conduits (embedded or exposed), ducts, duct banks, cable trays, electrical panels, among other applications. Due to their low smoke and toxic gas emission and flame retardant properties, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases when burning, recommended for installations in places with critical systems and equipment where greater reliability and less risk are required. It has collective protection in aluminised polyester tape and copper braid against electromagnetic interference. This cable has good flexibility, resistance to UV, weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF BTC ATOX HEPR/SHF1 - NBR 16442 control cable can be manufactured in other section, dimensions or material, at the customer's request.

    Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF BTA ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shield in aluminized polyester tape with tinned copper drain wire.
    4) Intermediate cover in thermoplastic compound free of halogen and flame retardant (SHF1).
    5) Shielding in galvanized steel braid.
    6) Non-hygroscopic tape.
    7) Cover in black halogen-free, flame-retardant thermoplastic compound (SHF1).

    - Insulation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in Alternate Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Non-halogenated control cables with low smoke emission for voltages up to 1 kV - Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signalling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others.
    They are applied in fixed systems of conduits (embedded or exposed), ducts, duct banks, cable trays, electrical panels, among other applications. Due to their low smoke and toxic gas emission and flame retardant properties, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases when burning, recommended for installations in places with critical systems and equipment where greater reliability and less risk are required. It has collective protection against electromagnetic interference and mechanical protection of galvanized steel braid. This cable has good flexibility, resistance to UV, bad weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF BTA ATOX HEPR/SHF1 - NBR 16442 control cables can be manufactured in other sections, dimensions or materials, at the customer's request.

    Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex).
    Special PVC resistant to oils, grease and other chemical products.
    LSZH (non-halogenated polyolefin compound)
    5- Perfectly round cover for cable gland applications in hazardous (Ex) areas.

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BTC ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Separator in polyester tape.
    4) Intermediate layer in thermoplastic compound, halogen free and flame retardant (SHF1).
    5) Shielding in bare copper braid.
    6) Non-hygroscopic tape.
    7) Cover in halogen free, flame retardant thermoplastic compound (SHF1) in black colour.

    -Isolation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    -Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in alternate current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Non-halogenated control cables with low smoke emission for voltages up to 1 kV - Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signalling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others.
    They are applied in fixed systems of conduits (embedded or exposed), ducts, duct banks, cable trays, electrical panels, among other applications. Due to their low smoke and toxic gas emission and flame retardant properties, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases when burning, recommended for installations in places with critical systems and equipment where greater reliability and less risk are required. It has EMV electromagnetic interference protection. This cable has good flexibility, resistance to UV, weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BTC ATOX HEPR/SHF1 - NBR 16442 control cables can be manufactured in other sections, dimensions or materials, at the customer's request.

    Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BTA ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Separator in polyester tape.
    4) Intermediate layer in thermoplastic compound, halogen free and flame retardant (SHF1).
    5) Shielding in galvanized steel braid.
    6) Non-hygroscopic tape.
    7) Cover in black halogen-free, flame-retardant thermoplastic compound (SHF1).

    - Insulation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in Alternate Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Non-halogenated control cables with low smoke emission for voltages up to 1 kV - Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signalling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others.
    They are applied in fixed systems of conduits (embedded or exposed), ducts, duct banks, cable trays, electrical panels, among other applications. Due to their low smoke and toxic gas emission and flame retardant properties, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases when burning, recommended for installations in places with critical systems and equipment where greater reliability and less risk are required. It has mechanical protection of galvanized steel braid. This cable has good flexibility, resistance to UV, bad weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BTA ATOX HEPR/SHF1 - NBR 16442 control cables can be manufactured in other sections, dimensions or materials, at the customer's request.

    Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BFA ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Separator in polyester tape.
    4) Intermediate layer in thermoplastic compound, halogen free and flame retardant (SHF1).
    5) Galvanized steel tape shield.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free, flame-retardant thermoplastic compound (SHF1) in black.

    - Insulation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in Alternate Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Non-halogenated control cables with low smoke emission for voltages up to 1 kV - Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signalling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others.
    They are applied in fixed systems of conduits (embedded or exposed), ducts, duct banks, cable trays, electrical panels, among other applications. Due to their low smoke and toxic gas emission and flame retardant properties, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases when burning, recommended for installations in places with critical systems and equipment where greater reliability and less risk are required. It has mechanical protection by galvanised steel strips. This cable has good flexibility, resistance to UV, bad weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BFA ATOX HEPR/SHF1 - NBR 16442 control cables can be manufactured in other sections, dimensions or materials, at the customer's request.

    Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BFC ATOX HEPR/SHF1 - NBR 16442

    1) Stranded conductor formed by electrolytic bare copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR - ethylene-propylene rubber) 90ºC.
    3) Separator in polyester tape.
    4) Intermediate layer in thermoplastic compound, halogen free and flame retardant (SHF1).
    5) Copper tape shield.
    6) Non-hygroscopic tape.
    7) Cover in halogen free, flame retardant thermoplastic compound (SHF1) in black colour.

    - Insulation voltage:
    Up to 1,0mm² - 500V
    From 1,50mm² to 10,00mm² - 1000V
    - Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electric tension in Alternate Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured on customer request with a green track (protective conductor). It can also be built with coloured veins.

    Applicable Specifications

    ABNT/MERCOSUR: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 - Non-halogenated control cables with low smoke emission for voltages up to 1 kV - Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signalling circuits of electrical equipment, structured cabling, machine connections, push buttons, power supply, microprocessor systems, in the automation of substations, power plants, industrial and chemical areas, among others.
    They are applied in fixed systems of conduits (embedded or exposed), ducts, duct banks, cable trays, electrical panels, among other applications. Due to their low smoke and toxic gas emission and flame retardant properties, they are recommended for installation in power supply and distribution circuits in places where there is a high concentration of people, as prescribed by NBR 5410 and NBR 13570 standards. They do not emit corrosive gases when burning, recommended for installations in places with critical systems and equipment where greater reliability and less risk are required. It has copper tape protection against electromagnetic interference. This cable has good flexibility, resistance to UV, bad weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BFC ATOX HEPR/SHF1 - NBR 16442 control cables can be manufactured in other sections, dimensions or materials, at the customer's request.

    Innovcable reserves the right to modify this catalogue without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture other configurations on request.
    1- Tinned Copper Conductor.
    Class 2 stranding.
    2- Different sections and number of veins, maximum up to
    - 71 x 0,50mm² / 71 x 2,50mm²
    - 52 x 4,00mm² / 52 x 4,00mm².
    - 42 x 6,00mm²
    - 20 x 10,0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A - 70 ºC
    PE - 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, grease and other chemicals.
    5- Cover perfectly cylindrical for applications with cable glands in classified areas (Ex).

    Download PDF Portuguese Download PDF EnglishDownload PDF Español