Flexible Special Control Cables

Halogen-free control cables

    INNOVCABLE LSZH JZ/OZ - H

    - Conductor material: bare copper wires
    - Conductor class: According to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    - Vein insulation: Halogen-free special compound (LSZH)
    - White or black veins identified by sequentially numbered black or yellow engraving with green earth (G).
    -Twisted in layers.
    - Outer cover in special halogen-free composite material (LSZH) manufactured in RAL grey 7001.
    - Free from silicone and harmful substances.
    - Rated voltage: 300/500V
    - Test voltage: 3000 V
    - Conductor resistance: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    - Insulation resistance: min. 20 MΩX Km.
    - min. bending radius fixed use:4 x d
    - min. bending radius if mobile: 15 x d
    - Flame retardant and halogen free, non-corrosive according to VDE 0482-332-1-1 (IEC 60332-3-24 Cat. C).

    Identification

    - All cables with identification (G) have 1 green conductor to earth, (x) without green conductor to earth.
    External identification marking:
    INNOVCABLE LSZH JZ/OZ H n (x) or (G) mm² 300/500V OF: XXXX/ANO

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    DIN VDE 0482-332-1-1 (IEC 60332-3-24 Cat. C)
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment in general, fixed and flexible applications without traction, can be applied in dry and wet locations. Halogen free, low smoke emission, does not emit toxic smoke, suitable for areas where there is concentration of people or values. It can be applied in external areas with UV application. Flame retardant and halogen free, non-corrosive according to VDE 0482-332-1-1 (IEC 60332-3-24 Cat. C). Manufactured free from noxious substances and silicone.

    Maximum Conductor Temperature

    Fixed: min-40° C / +90° C
    Mobile: min-5° C / +90° C
    - Conductor temperature +90°C in operation; 250°C in short circuit

    Notes

    G = with 1 green conductor to earth;
    x = no green conductor to earth (OZ).
    - Various other cable options and configurations can be produced on request. Innovcable reserves the right to change this catalogue without prior notice.

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE LSZH JZ/OZ - CH

    - Conductor material: bare copper wires
    - Conductor class: According to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    - Vein insulation: Halogen-free special compound (LSZH)
    - White or black veins identified by sequentially numbered black or yellow engraving with green earth (G).
    -Twisted in layers.
    - Shielding in tinned copper mesh, approx. 85% coverage.
    - Outer cover in special halogen-free composite material (LSZH) manufactured in RAL grey 7001.
    - Free of harmful substances and silicone.
    - Rated voltage: 300/500V
    - Test voltage: 3000 V
    - Conductor resistance: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    - Insulation resistance: min. 20 MΩX Km.
    - min. bending radius fixed use:4 x d
    - min. bending radius if mobile: 15 x d
    - Flame retardant and halogen free, non-corrosive according to VDE 0482-332-1-1 (IEC 60332-3-24 Cat. C).

    Identification

    - All cables with identification (G) have 1 green conductor to earth, (x) without green conductor to earth.
    External identification marking:
    INNOVCABLE LSZH JZ/OZ-CH n (x) or (G) mm² 300/500V OF: XXXX/ANO.

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    DIN VDE 0482-332-1-1 (IEC 60332-3-24 Cat. C).
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment in general, fixed and flexible applications without traction, can be applied in dry and wet locations. Halogen free, low smoke emission, does not emit toxic smoke, suitable for areas where there is concentration of people or values. It can be applied in external areas with UV application. Flame retardant and halogen free, non-corrosive according to VDE 0482-332-1-1 (IEC 60332-3-24 Cat. C). Manufactured free of harmful substances and silicone.
    Recommended for EMC applications. Shielding against electromagnetic interference.

    Maximum Conductor Temperature

    Fixed: min-40° C / +90° C
    Mobile: min-5° C / +90° C

    Notes

    G = with 1 green conductor to earth;
    x = no green conductor to earth (OZ).
    - Various other cable options and configurations can be produced on request. Innovcable reserves the right to change this catalogue without prior notice.

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE GIGAFLEX 500

    - Conductor material: bare copper wires
    - Conductor class: According to DIN VDE 0295 cl. 5, BS 6360 cl. 5 and IEC 60228 cl. 5
    - Vein insulation: Halogen-free (LSZH) special elastomeric compound (P10)
    - White or black veins identified by sequential numerical engraving in black or yellow with green earth (G) according to DIN VDE 0293.
    -Twisted in layers.
    - Outer layer in special halogen-free elastomeric compound (P10) (LSZH), manufactured in RAL grey 7001.
    - Made free of harmful substances and silicone.
    - Rated voltage: 300/500V
    - Test voltage: 3000 V
    - Conductor resistance: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    - Insulation resistance: min. 20 MΩX Km.
    - min. bending radius fixed use:4 x d
    - min. bending radius if mobile: 10 x d
    Bending test according to DIN VDE 0281-2.
    - Flame retardant and halogen free, non-corrosive according to VDE 0482-332-1-2 (IEC 60332-3-24 Cat. C), DIN EN/IEC 60332-1 (former DIN VDE 0472 part 804 test method B)
    LSZH= Low Smoke, Zero Halogen
    - Recyclable product

    Identification

    - All cables with identification (G) have 1 green conductor to earth, (x) without green conductor to earth.
    External identification marking:
    INNOVCABLE GIGAFLEX 500 n (x) or (G) mm² 300/500V 125 OF: XXXX/ANO

    Applicable Specifications

    VDE 0482 part 266-2-4/
    BS 4066 part 3/ EN 50266-2/ IEC 60332-3-24, (former DIN VDE 0472 part 804 test method C)
    DIN VDE 0482-332-1-2, DIN EN/IEC 60332-1 (former DIN VDE 0472 part 804 test method B)
    NF X 10-702
    DIN VDE 0482 part 267/ EN 50267-2-1/ IEC 60754-1 (equivalent to DIN VDE 0472 part 815)
    DIN VDE 0482 part 1034-1+2, DIN EN 61034-1+2/ IEC 61034-1+2, BS 7622 part 1+2 (previously DIN VDE 0472 part 816)
    VDE 0473 part 811-2-1
    DIN EN 60811-2-1 / DIN VDE 0281-2
    DIN EN 61234-1

    Applications

    Cable for power, control and connections of electrical equipment in general, fixed and flexible applications with low traction and high mechanical stress, can be applied in dry and wet locations. Halogen free, low smoke emission, does not emit toxic smoke, indicated for areas where there is concentration of people or values. Indicated for the construction of airports, cinemas, shopping malls, wind energy systems, naval constructions. It can be applied in external areas with UV protection and ozone resistance. Fire retardant, halogen free, non-corrosive, oil and grease resistant, abrasion and wear resistant, manufactured free of harmful substances and silicone.

    Maximum Conductor Temperature

    Fixed: min-40° C / +125° C
    Mobile: min -40° C / +125 ° C

    Notes

    G = with 1 green conductor to earth;
    x = without green conductor to earth.
    - Several other cable options and configurations can be produced on request. Innovcable reserves the right to modify this catalogue without prior notice.

    Download PDF Portuguese Download PDF EnglishDownload PDF Español

    INNOVCABLE GIGAFLEX 500-C

    - Conductor material: bare copper wires
    - Conductor class: According to DIN VDE 0295 cl. 5, BS 6360 cl. 5 and IEC 60228 cl. 5
    - Vein insulation: Halogen-free (LSZH) special elastomeric compound (P10)
    - White or black veins identified by sequential numerical engraving in black or yellow with green earth (G) according to DIN VDE 0293.
    -Twisted in layers.
    - Polyester tape separator.
    - Shielding in tinned copper mesh with approx. 85% coverage. (EMC protection)
    - Outer cover in special halogen-free (LSZH) elastomeric compound (P10), manufactured in RAL grey 7001.
    - Manufactured free of harmful substances and silicone.
    - Rated voltage: 300/500V
    - Test voltage: 3000 V
    - Conductor resistance: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    - Insulation resistance: min. 20 MΩX Km.
    - min. bending radius fixed use:4 x d
    - min. bending radius if mobile: 10 x d
    Bending test according to DIN VDE 0281-2.
    - Flame retardant and halogen free, non-corrosive according to VDE 0482-332-1-2 (IEC 60332-3-24 Cat. C), DIN EN/IEC 60332-1 (former DIN VDE 0472 part 804 test method B)
    - LSZH= Low Smoke, Zero Halogen
    - EMC = Electro Magnetic Compatibility
    - Recyclable product

    Identification

    - All cables with identification (G) have 1 green conductor to earth, (x) without green conductor to earth.
    External identification marking:
    INNOVCABLE GIGAFLEX 500-C n (x) or (G) mm² 300/500V 125°C OF: XXXX/ANO

    Applicable Specifications

    VDE 0482 part 266-2-4/
    BS 4066 part 3/ EN 50266-2/ IEC 60332-3-24, (former DIN VDE 0472 part 804 test method C)
    DIN VDE 0482-332-1-2, DIN EN/IEC 60332-1 (former DIN VDE 0472 part 804 test method B)
    NF X 10-702
    DIN VDE 0482 part 267/ EN 50267-2-1/ IEC 60754-1 (equivalent to DIN VDE 0472 part 815)
    DIN VDE 0482 part 1034-1+2, DIN EN 61034-1+2/ IEC 61034-1+2, BS 7622 part 1+2 (previously DIN VDE 0472 part 816)
    VDE 0473 part 811-2-1
    DIN EN 60811-2-1 / DIN VDE 0281-2
    DIN EN 61234-1

    Applications

    Cable for power, control and connections of electrical equipment in general, EMC protection against electromagnetic interference, fixed and flexible applications with low traction and high mechanical stress, can be applied in dry and wet locations. Halogen free, low smoke emission, does not emit toxic smoke, suitable for areas where there is concentration of people or values. Indicated for the construction of airports, cinemas, shopping malls, wind energy systems, naval constructions. It can be applied in external areas with UV protection and ozone resistance. Fire retardant, halogen free, non-corrosive, oil and grease resistant, abrasion and wear resistant, manufactured free of harmful substances and silicone.

    Maximum Conductor Temperature

    Fixed: min-40° C / +125° C
    Mobile: min -40° C / +125 ° C

    Notes

    G = with 1 green conductor to earth;
    x = without green conductor to earth.
    - Several other cable options and configurations can be produced on request. Innovcable reserves the right to modify this catalogue without prior notice.