Flexible Special Control Cables

Special Control Cables – PVC

    INNOVCABLE PVC JB/OB

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: special PVC 70°C – Up to 5 colored vein conductors in accordance with DIN VDE 0293-308; above 6 Innovcable color coded conductors with or without earth vein (G).
    -Twisted in layers.
    – External cover in special super flexible UV-resistant PVC, manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: up to 16.0mm² 300/500V; above 25.0mm² 0.6/1kv
    – Test voltage: 4,000 V
    – Short circuit voltage: Min. 8000V
    – Conductor resistance: in accordance with DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – min. Fixed use bending radius: 4 xd
    – min. bending radius if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification recording:
    INNOVCABLE JB/OB n (x) or (G) mm² 300/500V or 0.6/1kv 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment in general, fixed and flexible applications without traction, can be applied in dry and humid locations. Can be applied outdoors and has UV protection/resistance. Flame retardant and flame retardant in accordance with IEC 60332-1. Manufactured free of harmful substances and silicone.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JB/OB PLUS

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: special PVC 70°C – Up to 5 colored vein conductors in accordance with DIN VDE 0293-308; above 6 Innovcable color coded conductors with or without earth vein (G).
    -Twisted in layers.
    – External cover in special PVC resistant to oils, greases, acids, manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: up to 16.0mm² 300/500V; above 25.0mm² 0.6/1kv
    – Test voltage: 4,000 V
    – Short circuit voltage: Min. 8000V
    – Conductor resistance: in accordance with DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – min. Fixed use bending radius: 4 xd
    – min. bending radius if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification recording:
    INNOVCABLE JB/OB PLUS n (x) or (G) mm² 300/500V or 0.6/1kv 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment, with low loss in data transmission and signal transmission, for fixed and flexible applications without traction, can be applied in dry and humid locations. Has UV protection (external use). Flame retardant and flame retardant. Manufactured free of harmful substances and silicone.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JB/OB YCY

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: special PVC 70°C – Up to 5 colored vein conductors in accordance with DIN VDE 0293-308; above 6 Innovcable color coded conductors with or without earth vein (G).
    -Twisted in layers.
    – Protective intermediate cover in special PVC.
    – Shielding: tinned copper wire shielding, 85% coverage.
    – External cover in special PVC resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)).
    – Manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: up to 16.0mm² 300/500V; above 25.0mm² 0.6/1kv
    – Test voltage: 4,000 V
    – Short circuit voltage: Min. 8000V
    – Conductor resistance: in accordance with DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – Min radius. of curvature fixed use:6 xd
    – Min radius. of curvature if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification engraving: INNOVCABLE JB/OB-YCY n (x) or (G) mm² 300/500V or 0.6/1 Kv 70°C OF:XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment, with low loss in data transmission and signal transmission, for fixed and flexible applications without traction, can be applied in dry and humid locations. Has UV protection (external use). Flame retardant and flame retardant in accordance with IEC 60332-1. Resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)). Manufactured free of harmful substances and silicone. Protective shielding against electromagnetic interference. Recommended for EMC applications. 4000V voltage test. Additional mechanical protection through the intermediate frame.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JB/OB YSY

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: special PVC 70°C – Up to 5 colored vein conductors in accordance with DIN VDE 0293-308; above 6 Innovcable color coded conductors with or without earth vein (G).
    – Twisted in layers.
    – Protective intermediate cover in special PVC.
    – Armor: steel wires, 85% coverage.
    – External cover in special PVC resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)).
    – Manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: up to 16.0mm² 300/500V; above 25.0mm² 0.6/1kv
    – Test voltage: 4,000 V
    – Short circuit voltage: Min. 8000V
    – Conductor resistance: in accordance with DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – Min radius. of curvature fixed use:6 xd
    – Min radius. of curvature if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification recording:
    INNOVCABLE JB/OB-YSY n (x) or (G) mm² 300/500V or 0.6/1Kv 70°C OF:XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment, with excellent mechanical protection, for fixed and flexible applications without traction, can be applied in dry and humid locations. UV protection (external use). Flame retardant and flame retardant in accordance with IEC 60332-1. Resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)). Manufactured free of harmful substances and silicone. Triple protection, Steel wire armor for high mechanical protection and magnetic protection (oxidation-proof steel wires with additional internal shielding). 4000V voltage test.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JB/OB CY

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: special PVC 70°C – Up to 5 colored vein conductors in accordance with DIN VDE 0293-308; above 6 Innovcable color coded conductors with or without earth vein (G).
    -Twisted in layers.
    – Shielding: tinned copper wire shielding, 85% coverage.
    – External cover in special PVC resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)).
    – Manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: 300/500V
    – Voltage test: cable/cable 4,000 V; cable/shield 2,000 V
    – Capacitance: cable/cable ca. 120 nF/Km; cable/shield ca. 155 nF/Km.
    – Inductance: ca. 0.67 mH/Km
    – Conductor resistance: in accordance with DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – Min radius. of curvature fixed use: 6 xd
    – Min radius. of curvature if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification recording:
    INNOVCABLE JB/OB-CY n (x) or (G) mm² 300/500V 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment, with low loss in data transmission and signal transmission, for fixed and flexible applications without traction, can be applied in dry and humid locations. Has UV protection (external use). Flame retardant and flame retardant in accordance with IEC 60332-1. Resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)). Manufactured free of harmful substances and silicone. Protective shielding against electromagnetic interference. Recommended for EMC applications. 4000V voltage test.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JZ/OZ

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: Special PVC 70°C – White or black veins identified by sequential numerical engraving in black or yellow with or without earth green (G).
    – Twisted in layers.
    – External cover in special super flexible UV-resistant PVC, manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: 300/500V
    – Test voltage: 4,000 V
    – Short circuit voltage: Min. 8000V
    – Conductor resistance: in accordance with DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – min. Fixed use bending radius: 4 xd
    – min. bending radius if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification engraving:
    INNOVCABLE JZ/OZ n (x) or (G) mm² 300/500V 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment in general, fixed and flexible applications without traction, can be applied in dry and humid locations. Can be applied outdoors and has UV protection/resistance. Flame retardant and flame retardant in accordance with IEC 60332-1. Manufactured free of harmful substances and silicone.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF Portuguese
    Download PDF EnglishDownload PDF Español

    INNOVCABLE PVC JZ/OZ PLUS

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: Special PVC 70°C – White or black veins identified by sequential numerical engraving in black or yellow with or without earth green (G).
    – Twisted in layers.
    – External cover in special PVC resistant to oils, greases, acids, manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: 300/500V
    – Test voltage: 4,000 V
    – Short circuit voltage: Min. 8000V
    – Conductor resistance: in accordance with DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – min. Fixed use bending radius: 4 xd
    – min. bending radius if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification engraving:
    INNOVCABLE JZ/OZ PLUS n (x) or (G) mm² 300/500V 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment in general, fixed and flexible applications without traction, can be applied in dry and humid locations. Can be applied outdoors and has UV protection/resistance. Flame retardant and flame retardant in accordance with IEC 60332-1. Resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad). Manufactured free of harmful substances and silicone.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JZ/OZ YSY

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: Special PVC 70°C – White or black veins identified by sequential numerical engraving in black or yellow with or without earth green (G).
    – Twisted in layers.
    – Protective intermediate cover in special PVC.
    – Armor: steel wires, 85% coverage.
    – External cover in special PVC resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)).
    – Manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: 300/500V
    – Test voltage: 4,000 V
    – Short circuit voltage: Min. 8000V
    – Conductor resistance: in accordance with DIN VDE 0295 class 5e IEC 60228 cl. 5.
    – Insulation resistance: Minimum 20 MΩX Km.
    – Min radius. of curvature fixed use: 6 xd
    – Min radius. of curvature if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification engraving: INNOVCABLE JZ/OZ-YSY n (x) or (G) mm² 300/500V 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment, with excellent mechanical protection, for fixed and flexible applications without traction, can be applied in dry and humid locations. UV protection (external use). Flame retardant and flame retardant in accordance with IEC 60332-1. Resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)). Manufactured free of harmful substances and silicone. Triple protection, Steel wire armor for high mechanical protection and magnetic protection (oxidation-proof steel wires with additional internal shielding). 4000V Voltage Test

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JZ/OZ YCY

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: Special PVC 70°C – White or black veins identified by sequential numerical engraving in black or yellow with or without earth green (G).
    – Twisted in layers.
    – Protective intermediate cover in special PVC.
    – Shielding: tinned copper wire shielding, 85% coverage.
    – External cover in special PVC resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)).
    – Manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: 300/500V
    – Test voltage: 4,000 V
    – Conductor resistance: according to DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – Min radius. of curvature fixed use: 6 xd
    – Min radius. of curvature if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification engraving:
    INNOVCABLE JZ/OZ-YCY n (x) or (G) mm² 300/500V 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment, with low loss in data transmission and signal transmission, for fixed and flexible applications without traction, can be applied in dry and humid locations. Has UV protection (external use). Flame retardant and flame retardant in accordance with IEC 60332-1. Resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)). Manufactured free of harmful substances and silicone. Protective shielding against electromagnetic interference. Recommended for EMC applications. 4000V voltage test. Additional mechanical protection through the intermediate frame.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JZ/OZ CY TINY

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: thermoplastic compound based on polyvinyl chloride (PVC) 70ºC – White or black veins identified by sequential numerical engraving in black or yellow with or without earth green (G).
    -Twisted in layers.
    – Shielding: tinned copper wire shielding, 85% coverage.
    – External cover in thermoplastic compound based on polyvinyl chloride (PVC) flame retardant
    – Made in Gray RAL 7001.
    – Made free of harmful substances and silicone.

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification engraving:
    INNOVCABLE JZ/OZ-CY TINY n (x) or (G) mm² 300/500V 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment, with low loss in data transmission and signal transmission, for fixed and flexible applications without traction, can be applied in dry and humid locations. Has UV protection (external use). Flame retardant and flame retardant. Manufactured free of harmful substances and silicone. Protective shielding against electromagnetic interference. Recommended for EMC applications.

    Maximum Conductor Temperature

    +70ºC

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request.
    – Can be constructed with colored veins.
    Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JZ/OZ CY

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: Special PVC 70°C – White or black veins identified by sequential numerical engraving in black or yellow with or without earth green (G).
    -Twisted in layers.
    – Shielding: tinned copper wire shielding, 85% coverage.
    – External cover in special PVC resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)).
    – Manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: 300/500V
    – Voltage test: cable/cable 4,000 V; cable/shield 2,000 V.
    – Capacitance: cable/cable ca. 120 nF/Km; cable/shield ca. 155 nF/Km.
    – Inductance: ca. 0.67 mH/Km
    – Conductor resistance: in accordance with DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – Min radius. of curvature fixed use: 6 xd
    – Min radius. of curvature if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification recording:
    INNOVCABLE JZ/OZ-CY n (x) or (G) mm² 300/500V 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment, with low loss in data transmission and signal transmission, for fixed and flexible applications without traction, can be applied in dry and humid locations. Has UV protection (external use). Flame retardant and flame retardant in accordance with IEC 60332-1. Resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)). Manufactured free of harmful substances and silicone. Protective shielding against electromagnetic interference. Recommended for EMC applications. 4000V voltage test.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC YSLYSY-JZ

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: special PVC YI2
    – Vein colors: White or black veins identified by sequential numerical engraving in black or yellow with or without green earth (G) / (G) = with 1 green conductor for earth; (X) = no green conductor for earth.
    -Twisted in layers.
    – Intermediate cover: special PVC TM2, gray color (GR)
    – Frame: galvanized steel wire mesh.
    – External cover in special PVC TM2.
    – External cover manufactured in Transparent (TR) or Gray (GR)
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: 300/500V
    – Test voltage: cable/cable 3,000 V
    – Conductor resistance: according to DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – Min radius. of curvature fixed use: 6 xd
    – Min radius. of curvature if movable: 20 xd
    – Flame retardant in accordance with: VDE 0482-332-1-2/IEC 60332-1

    Identification

    Cable recording: INNOVCABLE YSLYSY-JZ n (x) or (G) mm² 300/500V +70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for control, power or instrumentation, reinforced with galvanized steel wire mesh. It can be used in fixed installations or flexible applications. Cable used for measurement, checking and control of industrial plants and engineering systems. It has unrestricted mobility without forcing movement control and without exposing it to tension stress. Can be applied in dry and humid locations with strict safety requirements

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor for earth.
    TR= Transparent
    GR= Gray
    – We can produce several other options and cable configurations upon request.
    – Innovcable reserves the right to change this catalog without prior notice.
    – Upon request we can manufacture at voltage of 0.6/1KV

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JZ/OZ BLACK 0.6/1kV

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: Special PVC 70°C – White or black veins identified by sequential numerical engraving in black or yellow with or without earth green (G).
    -Twisted in layers.
    – External cover in special PVC resistant to oils, greases, acids, manufactured in black.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: 0.6/1Kv.
    – Test voltage: 4,000 V
    – Conductor resistance: according to DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – min. Fixed use bending radius: 4 xd
    – min. bending radius if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    – External identification engraving:
    INNOVCABLE JZ/OZ BLACK n (x) or (G) mm² 0.6/1Kv 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment in general, for data transmission and signal transmission, fixed and flexible applications without traction, can be applied in dry and humid locations. Can be applied outdoors with UV application. Flame retardant and flame retardant in accordance with IEC 60332-1. Resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad). Manufactured free of harmful substances and silicone. Operating voltage 0.6/1kv. Test voltage of 4000V.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC JZ/OZ-YCY BLACK 0.6/1KV

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: Special PVC 70°C – White or black veins identified by sequential numerical engraving in black or yellow with or without earth green (G).
    -Twisted in layers.
    – Protective intermediate cover in special PVC.
    – Shielding: tinned copper wire shielding, 85% coverage.
    – External cover in special PVC resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)).
    – Manufactured in Black RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage: 0.6/1KV
    – Test voltage: 4,000 V
    – Conductor resistance: according to DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – Min radius. of curvature fixed use:6 xd
    – Min radius. of curvature if movable: 15 xd
    – Flame retardant and flame retardant in accordance with IEC 60332-1

    Identification

    – All cables with identification (G) have 1 green conductor for earth, (x) without green conductor for earth.
    External identification engraving:
    INNOVCABLE JZ/OZ-YCY BLACK n (x) or (G) mm² 0.6/1Kv 70°C OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 5
    IEC 60228 CLASS 5
    DIN VDE 0293
    RAL 7001
    IEC 60332-1
    DIN VDE 0245, 0250 AND 0281

    Applications

    Cable for power, control and connections of electrical equipment, for use in servo motor systems with frequency inverter technology, for fixed and flexible applications without traction, can be applied in dry and humid locations. Has UV protection (external use). Flame retardant and flame retardant in accordance with IEC 60332-1. Resistant to oils, greases, acids and radiation (up to 80x106cJ/Kg (up to 80 Mrad)). Operating voltage: 0.6/1kv. Manufactured free of harmful substances and silicone. Recommended for EMC applications. 4000V voltage test. Additional mechanical protection through the intermediate frame.

    Maximum Conductor Temperature

    min/max: -30°C / +70°C

    Notes

    G = with 1 green conductor for earth;
    x = no green conductor to earth (OZ).
    – We can produce several other cable options and configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE PVC TRAY VTC TC-ER

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: Special PVC for TC-ER application – White or black veins identified by sequential numerical engraving in black or yellow with or without green earth conductor (G).
    – Twisted in layers.
    – External cover in special PVC for TC-ER application, resistant to oils, grease, acids, movement, flame, weather, UV, northern lights, manufactured in Gray RAL 7001.
    – Manufactured free of harmful substances and silicone.
    – Nominal voltage:
    UL TC: 600V
    UL WTTC: 1000V
    UL AWM/ cRU AWM: 1000V
    – Test voltage: 2000V
    – Conductor resistance: according to DIN VDE 0295 class 5e IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – min. bending radius: 4 xd

    Identification

    INNOVCABLE PVC TRAY VTC 600V TC-ER ___ x ___AWG SUN RES DIR BUR ROHS OP

    Applicable Specifications

    UL: Impact and crushing
    TC-ER per UL 1277
    WTTC per UL 2277
    AWM 20886
    UL Oil Res I
    90°C humid; 90°C Dry
    Resistance to sunlight
    Aurora Borealis
    NFPA 79 2015
    NEC: Class 1 Division 2 per NEC Article 336, 392, 501
    cUL CIC FT4
    cRU AWM I/II A/B FT4
    CE & RoHS

    Applications

    Easy and economical installation cable due to no need to use conduit (suitable for open installation), in accordance with UL TC-ER & CSA CIC.
    The special PVC insulation for TC-ER applications is superior to PVC/Nylon products, in addition to allowing a reduction in dimensions.
    This product is resistant to torsion, oil, flame, cold, UV, northern lights and with mechanical resistance

    Maximum Conductor Temperature

    – UL TC /c(UL) CIC: -25°C to +90°C
    – Flexible use: -5° to +90°C
    – Fixed use: -40°C to +105°C

    Notes

    G = with 1 green conductor for earth;
    x = without green conductor for earth
    – We can produce several other options and cable configurations upon request.
    – Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE INNOVTRONIC-OZ EB LIYY-OZ

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Isolation: PVC esp. 105° C
    – White or black veins identified by sequential numbers according to VDE 0293 without green earth (G).
    – Twisted in layers.
    – External cover: special PVC resistant to oils, greases, acids.
    – Outer cover in Blue, RAL 5015.
    – Nominal voltage: 300/500V
    – Test voltage: 3,000 V
    – Conductor resistance: in accordance with VDE 0295 class 5 and IEC 60228 class 5.
    – Resist. of insulation: Min.20 MΩX Km.
    – Capacitance: 120nF/Km
    – Inductivity: ca. 0.65mH/Km
    – Min radius. fixed curvature: up to 12mm 5 xd> 12mm 7.5 xd
    – Min radius. of movable curvature: up to 12mm 10 xd up to 20mm 15 xd; . 20mm 20 x d.

    Identification

    INNOVCABLE – INNOVTRONIC-0Z EB LIYY-OZ nx 2 x mm² 300V OF: XXXX/YEAR.

    Applicable Specifications

    DIN VDE 0295 CLASS 4
    IEC 60228 CLASS 4
    “i” VDE 0165
    RAL 5015
    IEC 60332-1

    Applications

    • Cable for data transmission technology, control and connection of measurement controllers and instrumentation processes for lossless data and signal transmission.
    • For fixed applications and small movements. Has UV protection (external use).
    • Flame retardant and flame retardant in accordance with IEC 60332-1-2 and IEC 60332-3-24.
    • Resistant to oils, greases, acids. Suitable for dry and humid environments.
    • Intrinsically safe cable for electrical circuit protection class 'i' VDE 0165.
    • Intrinsically safe systems are circuits where no sparks and thermal effects in normal operation can ignite the surrounding areas.
    • <50 V AC and <75 V AC
    • It does not meet the requirements of 2006/95/EC- CE

    Maximum Conductor Temperature

    -30° C / +105° C
    – Flame retardant according to IEC 60332-1

    Notes

    – We can produce several other options and cable configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE INNOVTRONIC-OZ-CY EB LIYCY-OZ

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Isolation: PVC esp. 105° C
    – White or black veins identified by sequential numbers according to VDE 0293 without green earth (G).
    – Twisted in layers.
    – Tinned copper mesh shielding SN coverage of approximately 85%.
    – External cover: special PVC resistant to oils, greases, acids.
    – Outer cover in Blue, RAL 5015.
    – Nominal voltage: 300/500V
    – Test voltage: 3,000 V
    – Conductor resistance: in accordance with VDE 0295 class 5 and IEC 60228 class 5.
    – Resist. of insulation: Min.20 MΩX Km.
    – Capacitance: cable/cable 120nF/Km; cable/shield 160 nF/Km
    – Inductivity: ca. 0.65mH/Km
    – Min radius. fixed curvature: up to 12mm 5 xd> 12mm 7.5 xd
    – Min radius. of movable curvature: up to 12mm 10 xd up to 20mm 15 xd; . 20mm 20 x d.

    Identification

    INNOVCABLE – INNOVTRONIC-OZ-CY EB LIYCY-OZ nx 2 x mm² 300V OF:XXXX/YEAR.

    Applicable Specifications

    DIN VDE 0295 CLASS 4
    IEC 60228 CLASS 4
    “i” VDE 0165
    RAL 5015
    IEC 60332-1

    Applications

    • Cable for data transmission technology, control and connection of measurement controllers and instrumentation processes for lossless data and signal transmission.
    • For fixed applications and small movements.
    • Has UV protection (external use).
    • Flame retardant and flame retardant in accordance with IEC 60332-1-2 and IEC 60332-3-24.
    • Resistant to oils, greases, acids.
    • Suitable for dry and humid environments.
    • Intrinsically safe cable for electrical circuit protection class “i” VDE 0165.
    • Intrinsically safe systems are circuits where no sparks and thermal effects in normal operation can ignite the surrounding areas.
    • It does not meet the requirements of 2006/95/EC-CE.
    • < 50 V AC and < 75 V AC

    Maximum Conductor Temperature

    -30° C / +105° C
    – Flame retardant according to IEC 60332-1

    Notes

    – We can produce several other options and cable configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español

    INNOVCABLE CABLE FOR TRAFFIC SIGNALING BS 6346

    – Conductor material: bare copper wire
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Insulation: thermoplastic compound based on polyvinyl chloride (PVC) TI1.
    – Twisted in layers.
    – Intermediate layer: Polymeric compound with a tensile strength of not less than 4N / mm2 and an elongation break of not less than 50%.
    – Frame: galvanized steel wires, 85% coverage.
    – External cover in thermoplastic compound based on polyvinyl chloride (PVC) flame-retardant type TM1 in accordance with BS EN 50363
    – Made in Orange.
    – Manufactured free of harmful substances and silicone.

    • Insulation voltage: 600/1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    .- Voltage test: 4,000 V
    – Short circuit temperature: +160ºC
    – Voltage drop: mV/A/m
    1.00 mm²: 25
    1.50mm²: 38
    – Conductor resistance: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Insulation resistance: Minimum 20 MΩX Km.
    – min. Fixed use bending radius: 6 xD

    Identification

    Conductor colors:
    4 conductors: VD/VM/AM/AZ
    6 conductors: VD/VM/AM/AZ/BC/PT
    8 conductors: VD/VM/AM/AZ/BC/PT/CZ/LJ
    12 conductors: VD /VM/AM/AZ/BC/PT/CZ/LJ/MR/VL/RS/BJ

    Applicable Specifications

    DIN VDE 0295 class 5
    IEC 60228 cl. 5
    BS EN 50363
    BS 6346
    BS EN/IEC 60332-1-2
    BS EN 50364

    Applications

    For the interconnection of traffic signaling equipment or other applications that require mechanically robust conductor configurations.

    Maximum Conductor Temperature

    min/max: -15°C / +70°C

    Notes

    – We can produce several other options and cable configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download PDF PortugueseDownload PDF EnglishDownload PDF Español
    InnovCable
    Privacy Overview

    This website uses cookies so that we can provide the best user experience possible. Cookie information is stored in your browser and performs functions such as recognizing you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.