Control Cables – NBR 7289 / 7290 / 16442

Control cables – NBR 16442

    INNOVCABLE CONTROL CABLE SB ATOX HEPR/SHF1 – NBR 16442

    Control cable

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Polyester tape separator.
    4) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    • Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 – Non-halogenated, low-smoke control cables for voltages up to 1 kV – Performance requirements

    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others. Due to their
    properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive
    during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The INNOVCABLE CONTROL CABLE SB ATOX HEPR/SHF1 – NBR 16442, can be manufactured in another section, dimension or material at the customer's request. Innovcable reserves the right to change this catalog without prior notice.

    OTHER CONSTRUCTION OPTIONS:
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Material of the intermediate layer and cover:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemical products.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex)

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF ATOX HEPR/SHF1 – NBR 16442

    Ribbon Armored Control Cable

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
    4) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    • Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 –  Non-halogenated control cables with low smoke emission for voltages up to 1 kV – Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has collective protection in aluminized polyester tape against electromagnetic interference.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request. Innovcable reserves the right to change this catalog without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemicals.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF FC ATOX HEPR/SHF1 – NBR 16442

    Armored control cable on tape and copper tape

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
    4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
    5) Copper tape shielding.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    • Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 –  Non-halogenated control cables with low smoke emission for voltages up to 1 kV – Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. It has collective protection in aluminized polyester tape and copper tape against electromagnetic interference. This cable is resistant to UV, weather, humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF FC ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.

    Innovcable reserves the right to change this catalog without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemicals.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF FA ATOX HEPR/SHF1 – NBR 16442

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
    4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
    5) Galvanized steel strip shielding.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    • Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 –  Non-halogenated control cables with low smoke emission for voltages up to 1 kV – Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. It has collective protection against electromagnetic interference and mechanical protection using galvanized steel tape. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF FA ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.

    Innovcable reserves the right to change this catalog without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemicals.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF BTC ATOX HEPR/SHF1 – NBR 16442

    Aluminated polyester ribbon controlled control cable and copper braid

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
    4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
    5) Copper braid shielding.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    • Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 –  Non-halogenated control cables with low smoke emission for voltages up to 1 kV – Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has collective protection in aluminized polyester tape and copper braid against electromagnetic interference. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF BTC ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.

    Innovcable reserves the right to change this catalog without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemicals.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE CONTROL CABLE BF BTA ATOX HEPR/SHF1 – NBR 16442

    Aluminated polyester ribbon controlled control cable and steel braid

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
    4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
    5) Galvanized steel braid shielding.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    • Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 –  Non-halogenated control cables with low smoke emission for voltages up to 1 kV – Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has collective protection against electromagnetic interference and mechanical protection of galvanized steel braid. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BF BTA ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.

    Innovcable reserves the right to change this catalog without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemicals.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).
    Special PVC resistant to oils, greases and other chemicals.
    LSZH (non-halogenated polyolefin compound)
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex)

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE BTC ATOX HEPR/SHF1 CONTROL CABLE – NBR 16442

    Armored Copper braid control cable

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Polyester tape separator.
    4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
    5) Bare copper braid shielding.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    •Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    •Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 –  Non-halogenated control cables with low smoke emission for voltages up to 1 kV – Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has protection against EMV electromagnetic interference. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BTC ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.

    Innovcable reserves the right to change this catalog without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemicals.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE BTA ATOX HEPR/SHF1 CONTROL CABLE – NBR 16442

    Armored Copper braid control cable

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Polyester tape separator.
    4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
    5) Galvanized steel braid shielding.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    • Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 –  Non-halogenated control cables with low smoke emission for voltages up to 1 kV – Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has mechanical protection made of galvanized steel braid. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BTA ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.

    Innovcable reserves the right to change this catalog without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemicals.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE BFA ATOX HEPR/SHF1 CONTROL CABLE – NBR 16442

    Steel Ribbon Armored Control Cable

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Polyester tape separator.
    4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
    5) Galvanized steel strip shielding.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    • Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 –  Non-halogenated control cables with low smoke emission for voltages up to 1 kV – Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has mechanical protection made of galvanized steel tape. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BFA ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.

    Innovcable reserves the right to change this catalog without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemicals.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE BFC ATOX HEPR/SHF1 CONTROL CABLE – NBR 16442

    Steel Ribbon Armored Control Cable

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
    2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
    3) Polyester tape separator.
    4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
    5) Copper tape shielding.
    6) Non-hygroscopic tape.
    7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.

    • Insulation voltage:
    Up to 1.0mm² – 500V
    From 1.50mm² to 10.00mm² – 1000V
    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.

    Applicable Specifications

    ABNT/MERCOSUL: NM-280 and NM-IEC
    NBR NM IEC 60332-3-23 (Category B)
    ABNT: NBR 16442 –  Non-halogenated control cables with low smoke emission for voltages up to 1 kV – Performance requirements
    ABNT: NBR 6251

    Applications

    They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
    They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has copper tape protection against electromagnetic interference. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.

    Maximum Conductor Temperature

    In steady state: +90°C
    Maximum short circuit temperature: +250°C (5s)

    Notes

    The BFC ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.

    Innovcable reserves the right to change this catalog without prior notice.

    CONSTRUCTION OPTIONS
    We can manufacture upon request in other configurations.
    1- Tinned copper conductor.
    Class 2 stringing.
    2- Different sections and number of veins, maximum up to:
    • 71 x 0.50mm² / 71 x 2.50mm²
    • 52 x 4.00mm²
    • 42 x 6.00mm²
    • 20 x 10.0mm²
    3- Vein insulation material / other temperatures:
    PVC/E -105ºC
    PVC/A – 70 ºC
    PE – 80 ºC
    4- Cover material:
    PE
    PVC/E
    PVC/ST2
    Special PVC resistant to oils, greases and other chemicals.
    5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).

    Download Portuguese PDF Download PDF EnglishDownload PDF Español
    InnovCable
    Privacy Overview

    This website uses cookies so that we can provide the best user experience possible. Cookie information is stored in your browser and performs functions such as recognizing you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.