Control Cables – NBR 7289 / 7290 / 16442
Control cables – NBR 16442
INNOVCABLE CONTROL CABLE SB ATOX HEPR/SHF1 – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Polyester tape separator.
4) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
• Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
• Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance.
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others. Due to their
properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive
during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The INNOVCABLE CONTROL CABLE SB ATOX HEPR/SHF1 – NBR 16442, can be manufactured in another section, dimension or material at the customer's request. Innovcable reserves the right to change this catalog without prior notice.
OTHER CONSTRUCTION OPTIONS:
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Material of the intermediate layer and cover:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemical products.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex)
INNOVCABLE CONTROL CABLE BF ATOX HEPR/SHF1 – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
4) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
• Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
• Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance.
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has collective protection in aluminized polyester tape against electromagnetic interference.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The BF ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request. Innovcable reserves the right to change this catalog without prior notice.
CONSTRUCTION OPTIONS
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Cover material:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemicals.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).
INNOVCABLE CONTROL CABLE BF FC ATOX HEPR/SHF1 – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
5) Copper tape shielding.
6) Non-hygroscopic tape.
7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
• Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
• Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance.
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. It has collective protection in aluminized polyester tape and copper tape against electromagnetic interference. This cable is resistant to UV, weather, humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The BF FC ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.
Innovcable reserves the right to change this catalog without prior notice.
CONSTRUCTION OPTIONS
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Cover material:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemicals.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).
INNOVCABLE CONTROL CABLE BF FA ATOX HEPR/SHF1 – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
5) Galvanized steel strip shielding.
6) Non-hygroscopic tape.
7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
• Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
• Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. It has collective protection against electromagnetic interference and mechanical protection using galvanized steel tape. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The BF FA ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.
Innovcable reserves the right to change this catalog without prior notice.
CONSTRUCTION OPTIONS
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Cover material:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemicals.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).
INNOVCABLE CONTROL CABLE BF BTC ATOX HEPR/SHF1 – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
5) Copper braid shielding.
6) Non-hygroscopic tape.
7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
• Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
• Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance.
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has collective protection in aluminized polyester tape and copper braid against electromagnetic interference. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The BF BTC ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.
Innovcable reserves the right to change this catalog without prior notice.
CONSTRUCTION OPTIONS
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Cover material:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemicals.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).
INNOVCABLE CONTROL CABLE BF BTA ATOX HEPR/SHF1 – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Separator in polyester tape and collective shielding in aluminized polyester tape with tinned copper drain wire.
4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
5) Galvanized steel braid shielding.
6) Non-hygroscopic tape.
7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
• Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
• Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance.
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has collective protection against electromagnetic interference and mechanical protection of galvanized steel braid. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The BF BTA ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.
Innovcable reserves the right to change this catalog without prior notice.
CONSTRUCTION OPTIONS
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Cover material:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemicals.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).
Special PVC resistant to oils, greases and other chemicals.
LSZH (non-halogenated polyolefin compound)
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex)
INNOVCABLE BTC ATOX HEPR/SHF1 CONTROL CABLE – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Polyester tape separator.
4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
5) Bare copper braid shielding.
6) Non-hygroscopic tape.
7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
•Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
•Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance.
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has protection against EMV electromagnetic interference. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The BTC ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.
Innovcable reserves the right to change this catalog without prior notice.
CONSTRUCTION OPTIONS
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Cover material:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemicals.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).
INNOVCABLE BTA ATOX HEPR/SHF1 CONTROL CABLE – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Polyester tape separator.
4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
5) Galvanized steel braid shielding.
6) Non-hygroscopic tape.
7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
• Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
• Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance.
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has mechanical protection made of galvanized steel braid. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The BTA ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.
Innovcable reserves the right to change this catalog without prior notice.
CONSTRUCTION OPTIONS
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Cover material:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemicals.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).
INNOVCABLE BFA ATOX HEPR/SHF1 CONTROL CABLE – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Polyester tape separator.
4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
5) Galvanized steel strip shielding.
6) Non-hygroscopic tape.
7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
• Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
• Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance.
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has mechanical protection made of galvanized steel tape. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The BFA ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.
Innovcable reserves the right to change this catalog without prior notice.
CONSTRUCTION OPTIONS
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Cover material:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemicals.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).
INNOVCABLE BFC ATOX HEPR/SHF1 CONTROL CABLE – NBR 16442
1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 5 NBR NM 280 stranding.
2) Composite insulation (HEPR – ethylene propylene rubber) 90ºC.
3) Polyester tape separator.
4) Intermediate layer in halogen-free and flame retardant thermoplastic compound (SHF1).
5) Copper tape shielding.
6) Non-hygroscopic tape.
7) Cover in halogen-free and flame retardant thermoplastic compound (SHF1) in black.
• Insulation voltage:
Up to 1.0mm² – 500V
From 1.50mm² to 10.00mm² – 1000V
• Routine tests:
Electrical resistance of the conductor at 20ºC
Electrical voltage in Alternating Current
Insulation resistance.
Identification
Black or white veins numbered sequentially, can be manufactured at the customer's request with a green vein (protective conductor). It can also be constructed with colored veins.
Applicable Specifications
Applications
They are used in fixed installations in control, command and signaling circuits of electrical equipment, structured cabling, machine connections, button panels, power supply, microprocessed systems, in automation of substations, generating plants, industrial and chemical areas, among others.
They are applied in fixed conduit systems (embedded or exposed), channels, duct banks, cable trays, beds, electrical panels, among other applications. Due to their properties of low smoke and toxic gas emission and flame retardancy, they are recommended for installation in supply and distribution circuits in places where there is a large concentration of people, as prescribed by standards NBR 5410 and NBR 13570. They do not emit gases corrosive during burning, recommended for installations in places with critical systems and equipment where greater reliability and lower risk are required. It has copper tape protection against electromagnetic interference. This cable has good flexibility, resistance to UV, weather and humidity and certain chemicals.
Maximum Conductor Temperature
In steady state: +90°C
Maximum short circuit temperature: +250°C (5s)
Notes
The BFC ATOX HEPR/SHF1 – NBR 16442 CONTROL CABLE can be manufactured in another section, dimensional or material upon customer request.
Innovcable reserves the right to change this catalog without prior notice.
CONSTRUCTION OPTIONS
We can manufacture upon request in other configurations.
1- Tinned copper conductor.
Class 2 stringing.
2- Different sections and number of veins, maximum up to:
• 71 x 0.50mm² / 71 x 2.50mm²
• 52 x 4.00mm²
• 42 x 6.00mm²
• 20 x 10.0mm²
3- Vein insulation material / other temperatures:
PVC/E -105ºC
PVC/A – 70 ºC
PE – 80 ºC
4- Cover material:
PE
PVC/E
PVC/ST2
Special PVC resistant to oils, greases and other chemicals.
5- Perfectly cylindrical cover for cable gland applications in hazardous areas (Ex).