KNOWLEDGE ACADEMY
Lowest allowed bending radius – Lowest allowed bending radius – in accordance with DIN VDE 0298 part 3
Lowest allowed bending radius in accordance with DIN VDE 0298 part 3 Nominal voltage up to 0.6 / 1kV
Outer diameter of cable / Thickness of flat cable in mm | |||
Cables for fixed installation | up to 10mm | over/up to 10-25mm | over 25mm |
for fixed installation | 4xd | 4xd | 4xd |
for internal wiring | 1xd | 2xd | 3xd |
Flexible cables | Outer diameter of cable / Thickness of flat cable in mm up to over/up to over/up to over 8 mm 8-12 mm 12-20 mm 20 mm | |||||||||||
for fixed installation | 3 | x | d | 3 | x | d | 4 | x | d | 4 | x | d |
at free movement | 3 | x | d | 4 | x | d | 5 | x | d | 5 | x | d |
at introduction | 3 | x | d | 4 | x | d | 5 | x | d | 5 | x | d |
Flexible cables at restricted orientation | Outer diameter of cable / Thickness of flat cable in mm up to over/up to over/up to over 8 mm 8-12 mm 12-20 mm 20 mm | |||||||||||
drum operations | 5 | x | d | 5 | x | d | 5 | x | d | 6 | x | d |
Cable trolley operation | 3 | x | d | 4 | x | d | 5 | x | d | 5 | x | d |
Drag chain operations | 4 | x | d | 4 | x | d | 5 | x | d | 5 | x | d |
Roller deviation | 8 | x | d | 8 | x | d | 8 | x | d | 8 | x | d |