KNOWLEDGE ACADEMY

APPLICATION AND INSTALLATION OF MOVING CABLES – CRANES, CRANES, FESTOONS, ELEVATORS, CRANE BEATS…

    CURVATURE RADIUS


    These are the minimum bending radii for use in different applications. These recommendations must be strictly followed and the curvature calculated correctly in order to obtain the best result and durability of the cable. Never increase the minimum radius of curvature stipulated because it causes stretching and internal twisting, compromising the useful life. The frequency of movement must also be taken into account, because if there is low demand, the minimum radius of curvature may be tightened (slow or few movements)

    The table above provides the recommended minimum bend radii for different cable uses. Compliance with these recommendations and an accurate calculation of the bending radius are important as one of the most important reliability factors. Increasing the minimum bending radius has a more than proportional effect on the useful life of a cable because it causes stretching and internal twists due to the increase in mechanical stress on the conductors.

    INSTALLATION - CABLE GUIDE ANALYSIS

    • Always use guides that provide the best bending radius with the lowest possible deflection.
    • Always keep the guides aligned to avoid twisting.

    A one-way system appears to be more economically advantageous. However, a considerable increase in cable life is obtained if a two-way guide is used: This does not occur if the winding system is fed at the end, remaining in contact with the cable, regardless of the direction of movement of the machine.

    Whenever possible, use bidirectional or multiple guides, continuing the arc beyond the deflection angle. This way the minimum bending radius is always maintained.

     

     

    Avoid any abrupt changes in the bending radius, otherwise this could lead to cable breakage.

     

     

    Always use voltage protection systems when guiding the cable. Working voltages and protection devices must be defined according to parameters defined for each section of the cable.

    INSTALLATION - PULLEY ANALYSIS

    The weight of the pulleys increases inertia, requiring more torque to compensate, increasing tension on the cable, reducing its life. Also consider the contact of the cable's outer jacket with the pulley. Increase the contact area if using a hollow internal pulley.

    INCORRECT APPLICATION ON THE PULLEY: Effect induces twisting in the cable due to the rolling effect, reducing its useful life.

     

     

     

     

    CORRECT APPLICATION ON THE PULLEY: Way that minimizes the twist applied to the cable.

     

     

     

     

    INSTALLATION - CHANGING DIRECTION

    Be careful when changing direction, always leaving enough distance. It is recommended to use a distance of at least 20 times the external diameter of the cable (mainly in high-speed systems). This behavior recovers the cable's initial shape, before being subjected to fatigue again.

    INSTALLATION - ANCHORAGE SYSTEM

    In order to maintain the operating stability of the system, correct anchoring must be used. Different methods can be used, but there is one basic fundamental: spread the pulling forces over a large area of ​​the cable to avoid damage or failure at the anchor points.

    The most common mobile anchor points are cable grips. The load voltage must be distributed along the entire length of the cable between 20 to 25 x its total diameter. In order to maintain operational movements, leave a surplus of cables before entering the terminal box. When the center point inner fitting is installed, the vertical distance between the inlet mouth and the crane guide should not be less than 15 times the total cable diameter or 1m, whichever is greater. At least 2 turns of cable must be made around the fixed relief drum to ensure sufficient contact area for adequate stress to occur.

    Stress dynamics in the cable can lead to premature failure, especially in high-speed applications. To minimize this, you can use several solutions, but pay attention to the speed reduction device. It is interesting to apply this system to your spool movement project, reducing the speed before reaching the central point, and then re-accelerating after passing the central point and the direction of the spool of rotation has been reversed.


    1.  Cable support
    2. Entrance mouth
    3. Anti-stress bearing drum*
    4. Cable wound twice on anti-stress winding drum
    5. Power cord
    6. Terminal box
    7. Cable Tie

    *(For Medium Voltage cables= 10 x total diameter; For Low Voltage cables= 5 x total diameter)

    INSTALLATION - TYPES OF COILS (DRUMS)

    A well-designed winding system, together with the correct choice of cables, guarantees reliability and high durability. There are three main types of drums and they have advantages and disadvantages, let's see:

    1-) Mono Spiral Coil: it is the most common, it has a simple guide route that extends the life of the cable compared to other types. Also in these cable reels due to improved heat dissipation, the conductor size in power cables are generally smaller compared to other types of coils. The diameter and length of the cable is a main factor and must be considered for the application in mono-spiral coils: the good balance between the internal and external diameter of the spool will be critical to determine and control the tension of the cable.

    2-) Random Twist Coil: The simplest type of spool existing. It operates without guides and the random layers can create severe operational difficulties such as coil slippage, abrupt pulling force, twists, abrasions and abnormal accumulations. For these reasons, this application can only support small cable diameters and short runs: 250 m maximum run and an approximate weight <4 kg/m.

    3-) Multi Spiral Coil: Used when the cable has a large diameter and long lengths. The main advantage of using this type of reel is its ability to transport a large quantity of cable (even with large diameters) with constant winding tension and long distances. On the other hand, usually due to the location of the spool, it is also difficult to reduce the number of guides and changes of direction on this type of installation.

    COILS - HANDLING AND STORAGE

    Always use specialized personnel in order to obtain the best result. Test the entire system a few times before putting it into full operation in order to mitigate any failures that may occur.

    It is recommended to store and handle cables on their respective coils in order to avoid defects caused by loose cables.

    Avoid rolling the drums on their flanges, use a fork-lifter or crane to move the reel. If rolling cannot be avoided, do so against the winding direction in order to keep the cable firmly on the reel and prevent twisting or abrupt tensions.

    Always keep the cables on the original coils. Store in a cool, dry and covered place, and the ends of the cables should be closed, preferably with heat shrink wrap, to prevent the entry of moisture and dirt.

    Coil 11- In the case of lifting with a crane, you must use the correct rope connected to an axis placed in the center of the coil.* Attention:
    – Move as close to the ground.
    .- Move slowly and when in the correct location, do not make a sudden stop.

     


    Reel 22- In the case of a forklift, the drums must not be damaged by it.

    * Attention:
    – Place the coil in the center of the fork.
    – The width of the fork must be greater than the coil.

     


    Reel 33- Care when handling cables:
    • Do not cover the coils.
    • Do not roll more than 20 m.
    • Do not use sharp objects when moving.
    • Do not roll a damaged bobbin.
    • Do not roll on an uneven surface.
    • Do not store the coil near heaters or flammable places.

    CABLE INSTALLATION

    When transferring cables from wooden coils to system coils, try to transfer them directly without passing through rollers or changing directions. The transfer must be done slowly and with minimum tension: this behavior would avoid any torsional influence during cable installation.
    The following images show how to carry out the procedure:

    REMOVING THE TWIST:

    If, during the above procedure, the cable becomes twisted, it is strongly recommended to eliminate it. Normally two methods are foreseen to perform this action.
    1-) Wave movement:
    Insert a cylinder roll 6 to 8 inches under the cable near the twist. At this point, two people must walk holding the roller and pushing the “wave” towards the end of the cable. You can perform this action until the detected twist is removed.
    2-) Spiral Method:
    This procedure can occasionally be carried out by just one person. Leave a sufficient loose piece at the fixed end to obtain a spiral, which must be on the right or left side, depending on the direction of the twist detected. The spiral must be rolled onto the free end of the cable to remove any twist. Perform the same procedure for each twist. Once the problem has been resolved, place the cable again to start the operation. If you still find a small twist, perform the procedure again and cut approximately 50 cm of cable in order to eliminate the twist. Retest again and validate the test again.
    A properly installed cable without any twisting will remain stable in the system and will not twist throughout its service life. To detect whether kinks are occurring in the tests above, make some marks on the cable to detect possible kinks.
    Note: The marking may show a slight twist on long cable lengths, this is normal and will not be related to any type of twisting problem.

     CABLE INSTALLATION ON MULTI-SPIRAL COILS:
    INNOVCABLE crane cables are manufactured with conductors twisted to the right, consequently when winding on multi-spiral coils, the first turn must be with the cable against the right flange of the spool. This will naturally maintain the cable's forming trend.

    INSTALLATION - VERTICAL APPLICATIONS - REELFLEX (K)NSHTÖU-J / (N)SHTÖU-J # REELFLEX PUR-HF # FESTFLEX (N) GRDGÖU

    Anchoring systems:

    The best results are obtained with a stress relief coil. Open-end construction makes installation and relocation easier by providing better strain relief and outer jacket protection than squeezing the cable. Make at least 2 turns of cable around the drum. Table 1 (Radius of Curvature) shows the minimum bending radii for stress relief. If, on the other hand, anchoring is done by clamping over the sheath, a recommended length of sheath over the cable is approximately 25 times the total diameter of the cable. This will help spread the dynamic stresses over a sufficient surface area of ​​the outer jacket to inhibit damage to the cable.

     


    REELFLEX CABLE (K)NSHTÖU-J / (N)SHTÖU-J and REELFLEX PUR-HF

    When necessary, the lower part of these cables must be fixed with the correct tightening. The coverage of the outer jacket is the same as that of the anchoring system (up to 25 x cable diameter). The distance from the end of the anchoring device to the end of the machine's stroke must be at least 40 x the cable diameter. If frequent dynamic stresses near the anchor point are anticipated a spring may be used.

    F ESTFLEX (N) GRDGÖU – APPLICATIONS IN BASKET

    The correct basket used is important for the correct functioning of the system. High voltage applications involve long vertical lengths, high speed combined with moving ascent and descent and may have strong winds. Make sure the winding diameter is not less than 1.5 m. A guided central cone placed in the basket is recommended to collect the cable correctly.
     The shape of the basket and opening are also important operational factors: with high lift and high speed a height of at least 2 m and a conical opening is recommended.
    Try to place the cable in the basket in a counterclockwise direction from the outer layer of the original cable drum.

    ELECTRICAL PARAMETERS

    The electrical parameters are in accordance with DIN VDE 0298, part3 according to table 2.

    Voltage tests are used on flexible cables as required by DIN VDE 0250.

    CALCULATION OF THE CABLE CROSS SECTION

    For transmission of a given current under operating conditions, the current capacities for the continuous operating conditions discussed in this case must be adopted and corrected. Adjustment may be required through correction factors for conditions relating to:
    • room temperature
    • number of layers and number of turns on the coil
    • number of drivers
    It should not be forgotten that non-continuous operation will mean better cable performance.
    With the real trend towards increasing cable operating lengths it is interesting to check the voltage drop, not just for low voltages, but for medium and high voltages as well.
    In some circumstances, it may be necessary to check the cable's resistance to short circuit currents, both from a thermal point of view and electro-dynamically induced forces.

    CURRENT CAPACITY FOR CONTINUOUS OPERATION

    The values ​​below the direct current capacity and the correction factors are in accordance with VDE 0298 part 4, 08-2003. Calculations were made for a conductor temperature of 80°C.

    The calculation was made according to VDE as a precaution due to greater difficulties with heat dispersion for these types of cables. The values ​​are for three-conductor cables, with or without a ground conductor, without movement with the cable on the ground and at an ambient temperature of 30 °C. For installations where it is known that cable life will be reduced as a result of high mechanical stress or wear on the outer jacket thermal aging will be of less importance. In this case, a maximum operating temperature of 90 °c and the capacities given in table 3 may be considered increased by approximately 7%.


    Correction factors take into account installation and operating conditions, such as temperature, grouping, intermittency of use (amount of movements throughout the day) and number of conductors. Table 3 should be used for this.

    CURRENT CAPACITY FOR NON-CONTINUOUS OPERATION

    If the operation is non-continuous or partially continuous, it is advisable to check the circulation and operating time values ​​to see if the cable cross-section can be reduced.

    Example of intermittent operation with lifting equipment with repeated cycles: a 10-minute full load period of operation is followed by a longer period of no load. These 10 minutes taken as a percentage of the Total Duration (DT) of the cycle provides a percent load factor (FC).
    Load Factor FC % = (10 mi / DT) x 100
    In this case, the current load capacity calculated based on table 3 can be increased with the factors given in table 7.

    SHORT CIRCUIT CURRENT

     Short circuit thermal limit
    In accordance with VDE 0250 c standards. 8/75, the permissible thermal limits for short-circuit current in heavy mobile service cables must be calculated using the following reference values:
    Initial = 80°C (charge cable full)
    Final short circuit temperature = 200°C
    The short-circuit currents (thermal limit) given in table 8 were calculated using these reference values ​​and are valid for a time of 1 second.
    For other periods of time, taking into account the protection characteristics, the value in the table must be divided by the square root of the effective time (in seconds). For different initial and final temperatures (i.e. with 90°c and 250°c permissible according to standards), the short-circuit current (thermal limit) can be calculated using the following formula:

    ELECTRICAL PARAMETERS

     Three-phase voltage drop

    Voltage drop must be checked not only for low voltage but also for medium voltage where lengths are long. The value is calculated by multiplying the cable factors K (mV/Am) by the connection length L (in km).
    Formula to calculate voltage drop:
    V = I x L x K (Volt) where K =1.73 x (R cos + X sin )
    I = (A) current current capacity
    L = (km) connection length

    / km) ac conductor resistance at 80 ° C (see table 10) see table 10)

    and reactance 90°C, the resistance R must be multiplied by 1.03 whereas, for a frequency of 60Hz, the reactance X must be multiplied by 1.2 and the value to (mV/Am) recalculated.

    InnovCable
    Privacy Overview

    This website uses cookies so that we can provide the best user experience possible. Cookie information is stored in your browser and performs functions such as recognizing you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.