FIRE SYSTEMS CABLES – NBR 17240

Fire system cables – with and without shielding

    INNOVCABLE FIRE ALARM SB – 300V – NBR 17240

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 2 NBR NM 280 stranding
    2) Insulation in thermoplastic compound based
    on polyvinyl chloride (PVC/A) 70° C.
    3) Assembly of conductors in pairs or tender.
    Pair: Black / Red.
    Suit: Black / Red / White.
    4) Twist pitch: 50 to 65mm
    5) Polyester tape separator.
    6) Cover in thermoplastic compound based on polyvinyl chloride (PVC/A) in Red.

    • Insulation voltage: 300V – NBR 6148

    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    INNOVCABLE FIRE ALARM SB XX mm² 300V NBR 17240 OF:XXXX/YEAR.

    Applicable Specifications

    NBR – 6880 – Copper conductors for insulated cables – standardization
    NBR – 6148 – Insulated conductors with extruded polyvinyl chloride (PVC) insulation for voltages up to 750V – specification.
    NBR – 9441 – Execution of fire detection and alarm systems
    NBR 17240 – Fire detection and alarm systems – Design, installation, commissioning and maintenance of fire detection and alarm systems – Requirements
    NBR – 10898 – Emergency lighting system
    NBR – 13848 – Add manual
    NBR – 11836 – Smoke detector

    Applications

    They are used in fixed installations of fire alarm systems to conduct analog (4 – 20mA) and digital signals, point-to-point instrumentation, Hart ® protocol, connections of various sensors and meters, powering conventional and electronic relays, in industrial environments generally related to fire detection and alarm systems, intrusion security systems, remote measurement systems and emergency lighting systems.
    FIRE ALARM SB 300V cables are recommended for continuous installation with galvanized steel pipes. Cable built to comply with NBR 17240.
    Excellent flexibility, resistance to chemicals, humidity and UV rays, flame retardant and self-extinguishing, complying with vertical flame propagation tests, in accordance with NBR NM IEC 60332-3-23, category B.

    Maximum Conductor Temperature

    Conductor temperature in continuous operation: 70ºC (PVC/A)

    – Can be made with other insulation:
    Vein insulation material / other temperatures:
    PVC/E – 105ºC
    XLPE – 125 ºC or 90 ºC
    HEPR – 90 ºC

    Notes

    WE CAN MANUFACTURE OTHER CONFIGURATIONS ON REQUEST:
    1- Tinned copper conductor.
    Stringing class 1, 4 or 5.
    Court Training.
    2- Different sections and number of veins.

    3-
    Vein insulation material

    /

    other
    temperatures
    :
    PVC
    / E -105ºC resistant to oils, greases and other chemicals. LSZH (non-halogenated polyolefin compound)
    5- Perfectly cylindrical cover for applications with cable glands in hazardous areas (Ex)
    6- Insulation voltage: 300V, 750V or 0.6/1KV.
    Innovcable reserves the right to change this catalog without prior notice.

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE FIRE ALARM SB – 600V – NBR 17240

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 2 NBR NM 280 stranding
    2) Insulation in thermoplastic compound based
    on polyvinyl chloride (PVC/A) 70° C.
    3) Assembly of conductors in pairs or tender.
    Pair: Black / Red.
    Suit: Black / Red / White.
    4) Twist pitch: 50 to 65mm
    5) Polyester tape separator.
    6) Cover in thermoplastic compound based on polyvinyl chloride (PVC/A) in Red.

    • Insulation voltage: 600V – NBR 6148

    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    INNOVCABLE FIRE ALARM SB XX mm² 600V NBR 17240 OF:XXXX/YEAR.

    Applicable Specifications

    NBR – 6880 – Copper conductors for insulated cables – standardization
    NBR – 6148 – Insulated conductors with extruded polyvinyl chloride (PVC) insulation for voltages up to 750V – specification.
    NBR – 9441 – Execution of fire detection and alarm systems
    NBR 17240 – Fire detection and alarm systems – Design, installation, commissioning and maintenance of fire detection and alarm systems – Requirements
    NBR – 10898 – Emergency lighting system
    NBR – 13848 – Add manual
    NBR – 11836 – Smoke detector

    Applications

    They are used in fixed installations of fire alarm systems to conduct analog (4 – 20mA) and digital signals, point-to-point instrumentation, Hart ® protocol, connections of various sensors and meters, powering conventional and electronic relays, in industrial environments generally related to fire detection and alarm systems, intrusion security systems, remote measurement systems and emergency lighting systems.
    FIRE ALARM SB 600V cables are recommended for continuous installation with galvanized steel pipes. Cable built to comply with NBR 17240.
    Excellent flexibility, resistance to chemicals, humidity and UV rays, flame retardant and self-extinguishing, complying with vertical flame propagation tests, in accordance with NBR NM IEC 60332-3-23, category B.

    Maximum Conductor Temperature

    Conductor temperature in continuous operation: 70ºC (PVC/A)

    – Can be made with other insulation:
    Vein insulation material / other temperatures:
    PVC/E – 105ºC
    XLPE – 125 ºC or 90 ºC
    HEPR – 90 ºC

    Notes

    WE CAN MANUFACTURE OTHER CONFIGURATIONS ON REQUEST:
    1- Tinned copper conductor.
    Stringing class 1, 4 or 5.
    Court Training.
    2- Different sections and number of veins.

    3-
    Vein insulation material

    /

    other
    temperatures
    :
    PVC
    / E -105ºC resistant to oils, greases and other chemicals. LSZH (non-halogenated polyolefin compound)
    5- Perfectly cylindrical cover for applications with cable glands in hazardous areas (Ex)
    6- Insulation voltage: 300V, 750V or 0.6/1KV.
    Innovcable reserves the right to change this catalog without prior notice.

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE FIRE ALARM BF – 300V – NBR 17240

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 2 NBR NM 280 stranding
    2) Insulation in thermoplastic compound based
    on polyvinyl chloride (PVC/E) 105° C.
    3) Assembly of conductors in pairs or tender.
    Pair: Black / Red
    Suit: Black / Red / White
    4) Twist pitch: 50 to 65mm
    5) Separator in polyester tape and collective shielding in aluminized polyester tape, with flexible drain conductor of 0.5 mm² section, formed by tinned electrolytic copper wires.
    6) Cover in thermoplastic compound based on polyvinyl chloride (PVC/ST1) in Red.

    • Insulation voltage: 300V – NBR 6148

    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    INNOVCABLE FIRE ALARM BF XX mm² 300V 105°C NBR 17240 OF:XXXX/YEAR.

    Applicable Specifications

    NBR – 6880 – Copper conductors for insulated cables – standardization
    NBR – 6148 – Insulated conductors with extruded polyvinyl chloride (PVC) insulation for voltages up to 750V – specification.
    NBR – 9441 – Execution of fire detection and alarm systems
    NBR 17240 – Fire detection and alarm systems – Design, installation, commissioning and maintenance of fire detection and alarm systems – Requirements
    NBR – 10898 – Emergency lighting system
    NBR – 13848 – Add manual
    NBR – 11836 – Smoke detector

    Applications

    They are used in fixed installations of fire alarm systems to conduct analog (4 – 20mA) and digital signals, point-to-point instrumentation, Hart ® protocol, connections of various sensors and meters, powering conventional and electronic relays, in industrial environments generally related to fire detection and alarm systems, intrusion security systems, remote measurement systems and emergency lighting systems.
    FIRE ALARM BF 300V cables are recommended for cases where excellent levels of protection against external electromagnetic interference are required, and maximum immunity against the appearance of “crosstalk” (crosstalk) between the different pairs/terminals, providing electrical discharge thereof. Cable built to comply with NBR 17240.
    Excellent flexibility, resistance to chemicals, humidity and UV rays, flame retardant and self-extinguishing, complying with vertical flame propagation tests, in accordance with NBR NM IEC 60332-3-23, category B.

    Maximum Conductor Temperature

    In continuous regime: 105ºC (PVC/E)

    – Can be made with other insulation:
    Vein insulation material / other temperatures:
    PVC/A -70ºC
    XLPE – 125 ºC or 90 ºC
    HEPR – 90 ºC
    PE – 80 ºC

    Notes

    WE CAN MANUFACTURE OTHER CONFIGURATIONS ON REQUEST:
    1- Tinned copper conductor.
    Stringing class 1, 4 or 5.
    2- Different sections and number of veins.

    3-
    Vein insulation material

    /

    other
    temperatures
    : PVC
    /
    A -70ºC resistant to oils, greases and other chemicals. LSZH (non-halogenated polyolefin compound)
    5- Perfectly cylindrical cover for applications with cable glands in hazardous areas (Ex)
    6- Insulation voltage: 600V, 750V, 0.6/1KV among others.

    Innovcable reserves the right to change this catalog without prior notice.

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE FIRE ALARM BF – 600V – NBR 17240

    1) Stranded conductor formed by bare electrolytic copper wires, soft temper, class 2 NBR NM 280 stranding
    2) Insulation in thermoplastic compound based
    on polyvinyl chloride (PVC/A) 70° C.
    3) Assembly of conductors in pairs or tender.
    Pair: Black / Red.
    Suit: Black / Red / White.
    4) Twist pitch: 50 to 65mm
    5) Separator in polyester tape and collective shielding in aluminized polyester tape, with flexible drain conductor of 0.5 mm² section, formed by tinned electrolytic copper wires.
    6) Cover in thermoplastic compound based on polyvinyl chloride (PVC/E) 105° C in red.

    • Insulation voltage: 600V – NBR 6148

    • Routine tests:
    Electrical resistance of the conductor at 20ºC
    Electrical voltage in Alternating Current
    Insulation resistance.

    Identification

    INNOVCABLE FIRE ALARM BF XX mm² 600V 70°C NBR 17240 OF:XXXX/YEAR.

    Applicable Specifications

    NBR – 6880 – Copper conductors for insulated cables – standardization
    NBR – 6148 – Insulated conductors with extruded polyvinyl chloride (PVC) insulation for voltages up to 750V – specification.
    NBR – 9441 – Execution of fire detection and alarm systems
    NBR 17240 – Fire detection and alarm systems – Design, installation, commissioning and maintenance of fire detection and alarm systems – Requirements
    NBR – 10898 – Emergency lighting system
    NBR – 13848 – Add manual
    NBR – 11836 – Smoke detector

    Applications

    They are used in fixed installations of fire alarm systems to conduct analog (4 – 20mA) and digital signals, point-to-point instrumentation, Hart ® protocol, connections of various sensors and meters, powering conventional and electronic relays, in industrial environments generally related to fire detection and alarm systems, intrusion security systems, remote measurement systems and emergency lighting systems.
    FIRE ALARM BF 600V cables are recommended for cases where excellent levels of protection against external electromagnetic interference are required, and maximum immunity against the appearance of “crosstalk” (crosstalk) between the different pairs/terminals, providing electrical discharge to them. Cable built to comply with NBR 17240.
    Excellent flexibility, resistance to chemicals, humidity and UV rays, flame retardant and self-extinguishing, complying with vertical flame propagation tests, in accordance with NBR NM IEC 60332-3-23, category B.

    Maximum Conductor Temperature

    Continuous conductor temperature: 70ºC (PVC/A)
    External jacket temperature: 105ºC (PVC/E).

    – Can be made with other insulation:
    Vein insulation material / other temperatures:
    PVC/A -70ºC
    XLPE – 125 ºC or 90 ºC
    HEPR – 90 ºC
    PE – 80 ºC

    Notes

    WE CAN MANUFACTURE OTHER CONFIGURATIONS ON REQUEST:
    1- Tinned copper conductor.
    Stringing class 1, 4 or 5.
    Court Training.
    2- Different sections and number of veins.

    3-
    Vein insulation material

    /

    other
    temperatures
    :
    PVC
    / E -105ºC resistant to oils, greases and other chemicals. LSZH (non-halogenated polyolefin compound)
    5- Perfectly cylindrical cover for applications with cable glands in hazardous areas (Ex)
    6- Insulation voltage: 300V, 750V or 0.6/1KV.
    Innovcable reserves the right to change this catalog without prior notice.

    Download Portuguese PDF Download PDF EnglishDownload PDF Español
    InnovCable
    Privacy Overview

    This website uses cookies so that we can provide the best user experience possible. Cookie information is stored in your browser and performs functions such as recognizing you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.