Intrinsically safe cables

Intrinsic safety electronic cables

    INNOVCABLE INNOVTRONIC OZ EB LIYY-OZ

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Isolation: PVC esp. 105° C
    – White or black veins identified by sequential numbers according to VDE 0293 without green earth (G).
    – Twisted in layers.
    – External cover: special PVC resistant to oils, greases, acids.
    – Outer cover in Blue, RAL 5015.
    – Nominal voltage: 300/500V
    – Test voltage: 3,000 V
    – Conductor resistance: in accordance with VDE 0295 class 5 and IEC 60228 class 5.
    – Resist. of insulation: Min.20 MΩX Km.
    – Capacitance: 120nF/Km
    – Inductivity: ca. 0.65mH/Km
    – Min radius. fixed curvature: up to 12mm 5 xd> 12mm 7.5 xd
    – Min radius. of movable curvature: up to 12mm 10 xd up to 20mm 15 xd; . 20mm 20 x d.

    Identification

    INNOVCABLE – INNOVTRONIC-0Z EB LIYY-OZ nx 2 x mm² 300V OF: XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 4
    IEC 60228 CLASS 4
    “i” VDE 0165
    RAL 5015
    IEC 60332-1

    Applications

    • Cable for data transmission technology, control and connection of measurement controllers and instrumentation processes for lossless data and signal transmission.
    • For fixed applications and small movements.
    • Has UV protection (external use).
    • Flame retardant and flame retardant in accordance with IEC 60332-1-2 and IEC 60332-3-24.
    • Resistant to oils, greases, acids.
    • Suitable for dry and humid environments.
    • Intrinsically safe cable for electrical circuit protection class “i” VDE 0165.
    • Intrinsically safe systems are circuits where no sparks and thermal effects in normal operation can ignite the surrounding areas.
    • <50 V AC and <75 V AC
    • It does not meet the requirements of 2006/95/EC-CE.

    Maximum Conductor Temperature

    -30° C / +105° C
    – Flame retardant according to IEC 60332-1

    Notes

    – We can produce several other options and cable configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download Portuguese PDF Download PDF EnglishDownload PDF Español

    INNOVCABLE INNOVTRONIC OZ-CY EB LIYCY-OZ

    – Conductor material: bare copper wires
    – Conductor class: according to DIN VDE 0295 class 5 and IEC 60228 cl. 5
    – Vein Isolation: PVC esp. 105° C
    – White or black veins identified by sequential numbers according to VDE 0293 without green earth (G).
    – Twisted in layers.
    – Tinned copper mesh shielding SN coverage of approximately 85%.
    – External cover: special PVC resistant to oils, greases, acids.
    – Outer cover in Blue, RAL 5015.
    – Nominal voltage: 300/500V
    – Test voltage: 3,000 V
    – Conductor resistance: in accordance with VDE 0295 class 5 and IEC 60228 class 5.
    – Resist. of insulation: Min.20 MΩX Km.
    – Capacitance: cable/cable 120nF/Km; cable/shield 160 nF/Km
    – Inductivity: ca. 0.65mH/Km
    – Min radius. fixed curvature: up to 12mm 5 xd> 12mm 7.5 xd
    – Min radius. of movable curvature: up to 12mm 10 xd up to 20mm 15 xd; . 20mm 20 x d.

    Identification

    INNOVCABLE – INNOVTRONIC-0Z-CY EB LIYCY-OZ nx 2 x mm² 300VOF:XXXX/YEAR

    Applicable Specifications

    DIN VDE 0295 CLASS 4
    IEC 60228 CLASS 4
    “i” VDE 0165
    RAL 5015
    IEC 60332-1

    Applications

    • Cable for data transmission technology, control and connection of measurement controllers and instrumentation processes for lossless data and signal transmission.
    • For fixed applications and small movements.
    • Has UV protection (external use).
    • Flame retardant and flame retardant in accordance with IEC 60332-1-2 and IEC 60332-3-24.
    • Resistant to oils, greases, acids.
    • Suitable for dry and humid environments.
    • Intrinsically safe cable for electrical circuit protection class “i” VDE 0165.
    • Intrinsically safe systems are circuits where no sparks and thermal effects in normal operation can ignite the surrounding areas.
    •  <50 V AC and <75 V AC
    • It does not meet the requirements of 2006/95/EC-CE.

    Maximum Conductor Temperature

    -30° C / +105° C
    – Flame retardant according to IEC 60332-1

    Notes

    – We can produce several other options and cable configurations upon request. Innovcable reserves the right to change this catalog without prior notice.

    Download Portuguese PDF Download PDF EnglishDownload PDF Español
    InnovCable
    Privacy Overview

    This website uses cookies so that we can provide the best user experience possible. Cookie information is stored in your browser and performs functions such as recognizing you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.