ACADEMY OF KNOWLEDGE

Current Ratings & Volt Drop - IEE

TABLE 4A2 Schedule of appropriate current ratings tables - IEE

Specification number Specification TitleApplicable Current Rating TablesConductor Operating Temperature
BS5467:1997Specification for 600/1000V & 1900/3300V armoured electric cables having thermosetting insulation4E3, 4E4, 4L3, 4L490ºC
BS6004:2000Electric cables. PVC insulated, non-armoured cables for voltages up to and including 450/750V, for electric power, lighting & internal wiring4D1, 4D2, 4E170ºC, 90ºC
PVC insulated & sheathed flat cable with protective conductor to Table 84D570ºC
BS6207-1:1995Mineral insulated cables with a rated voltage not exceeding 750V4J1, 4J270ºC*, 105ºC*
BS6346:1997Specification for 600/1000V & 1900/3300V armoured electric cables having PVC insulation4D3, 4D4, 4K3, 4K470ºC
BS6500:2000Electric cbales. Flexible cords rated up to 300/500V, for use with appliances and equipment intended for domestic, office and similar environments4H360ºC, 90ºC
BS6724:1997Specification for 600/1000V & 1900/3300Varmoured electric cables having thermosetting insulation and low emission of smoke and corrosive gases when affected by fire4E3, 4E4, 4L3, 4L490ºC
BS6883:1999Elastomer insulated cables for fixed wiring in ships and on mobile & fixed offshore units. Requirements & test methods4F1, 4F285ºC
BS7211:1998Specification for thermosetting insulated cables (non-armoured) for electric power & lighting with low emission of smoke & corrosive gases when affected by fire4E1, 4E290ºC
BS7629-1:1997Specification for 300/500V fire resistant electric cables having low emission of smoke & corrosive gases when affected by fire. Multicore cables4D270ºC
BS7846:2000Electric cables. 600/1000V armoured fire-resistant electric cables having thermosetting insulation & low emission of smoke and corrosive gases when affected by fire4E490ºC
BS7889:1997Specification for 600/1000V single-core unarmoured electric cables having thermosetting insulation4E1, 4L190ºC
BS7919:2001Electric cables. Flexible cables rated up to 450/750V, for use with appliances & equipment intended for industrial & similar environments4H1, 4H2, 4H360ºC, 110ºC
BS8436:2004300/500V screened electric cables having low emission of smoke & corrosive gases when affected by fire, for use in thin partitions and building voids4D270ºC
BSEN60702-1:2001Mineral insulated cables and their terminations with a rated voltage not exceeding 750V. Cables4J1, 4J270ºC*, 105ºC*
 * sheath operating temperature

TABLE 4A3 Schedule of appropriate current ratings tables - IEE

Specification NumberSpecification TitleApplicable Current Rating Tables (16th edition tables)Conductor Operating Temperature
BS5467:1997Electric cables - thermosetting insulated armoured cables for voltages of 600/1000V & 1900/3300V4E3, 4E4, 4J3, 4J4 (4L3, 4L4)90ºC
BS6004:2000Electric cables - PVC insulated, non-armoured cables for voltages up to and including 450/750V, for electric power, lighting & internal wiring4D1, 4D270ºC
Thermoplastic insulated & sheathed flat cable with protective conductor to Table 84D570ºC
BS6231Electic cables - single-core PVC insulated flexible cables of rated voltage 600/1000Vfor switchgear & controlgear wiring4D170ºC*.
BS6346:1997Electric cables - PVC insulated, armoured cables for voltages of 600/1000V & 1900/3300V4D3, 4D4, 4H3, 4H4 (4K3, 4K4), 4J3, 4J470ºC
BS6500:2000Electric cbales - Flexible cords rated up to 300/500V, for use with appliances and equipment intended for domestic, office and similar environments4F3 (4H3)60ºC, 90ºC
BS6724:1997Electric cables - thermosetting insulated, armoured cables for voltages of 600/1000V & 1900/3300V having low emission of smoke and corrosive gases when affected by fire4E3, 4E4, 4J3, 4J4 (4L3, 4L4)90ºC
BS7211:1998Electric cables - thermosetting insulated non-armoured cables for voltages up to and including 450-750V for electric power, lighting & internal wiring and having low emission of smoke & corrosive gases when affected by fire4E290ºC
BS7629-1:1997Specification for 300/500V fire resistant electric cables having low emission of smoke & corrosive gases when affected by fire. Multicore cables4D270ºC
BS7846:2000Electric cables - 600/1000V armoured fire-resistant electric cables having thermosetting insulation & low emission of smoke and corrosive gases when affected by fire4E3, 4E4, 4J3, 4J490ºC
BS7889:1997Electric cables - thermosetting insulated, armoured cables for a voltatge of 600/1000V4E190ºC
BS7919:2001Electric cables - Flexible cables rated up to 450/750V, for use with appliances & equipment intended for industrial & similar environments4F1, 4F2, 4F3, (4H1, 4H2, 4H3)60ºC, 90ºC
BS8436:2004Electric cables - 300/500V screened electric cables having low emission ofsmoke & corrosive gases when affected by fire, for use in walls, partitions and building voids - multicore cables4D270ºC
BSEN60702-1:2001Mineral insulated cables and their terminations with a rated voltage not exceeding 750V. Cables4G1, 4G2 (4J1, 4J2)70ºC**, 105ºC**
* cables to BS6231 when installed in conduit or trunking are rated to 70ºC
** sheath operating temperature

Table 4D1A PVC Insulation / Copper / Single-core / Non-armoured - IEE

  • Standard: BS 7671
  • Table 4D1A
  • Single-core 70 °C thermoplastic insulated cables, non armoured, with or without sheath
  • Copper conductors
  • Conductor temperature: 70 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method A
(enclosed in conduit
in thermally insulated
wall etc.)
Reference Method B
(enclosed in conduit
on a wall or in
trunking etc.)
Reference Method C
(Clipped direct)
Reference Method F
(in free air or in perforated cable tray horizontal or vertical)
TouchingSpaced
by one diameter
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
flat
3 cables,
three-
phase AC
flat
3 cables,
three-
phase AC
trefoil
2 single-phase cables
AC or DC or 3 cables
three-phase AC flat
HorizontalVertical
1234567891011
123456789101112
11110.513.51215.514-----
1.514.513.517.515.52018-----
2.5201824212725-----
4262432283733-----
6343141364743-----
10464257506559-----
16615676688779-----
25807310189114104131114110146130
359989125110141129162143137181162
50119108151134182167196174167219197
70151136192171234214251225216281254
95182164232207284261304275264341311
120210188269239330303352321308396362
150240216300262381349406372356456419
185273245341296436400463427409521480
240321286400346515472546507485615569
300367328458394594545629587561709659
400--546467694634754689656852795
500--626533792723868789749982920
630--720611904826100590585511381070
800----10309431086102097112651188
1000----1154105812161149107914201337

Table 4D2A PVC Insulation / Copper / Multi-core / Non-armoured - IEE

  • Standard : BS 7671
  • Table 4D2A
  • Multi-core 70 °C thermoplastic insulated and thermoplastic sheathed cables, non armoured
  • Copper conductors
  • Conductor temperature: 70 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method A
(enclosed in conduit
in thermally insulated
wall etc.)
Reference Method B
(enclosed in conduit
on a wall or in
trunking etc.)
Reference Method C
(Clipped direct)
Reference Method E
(in free air or
in perforated cable tray
horizontal or vertical)
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
12345678
123456789
111101311.51513.51714.5
1.5141316.51519.517.52218.5
2.518.517.5232027243025
42523302736324034
63229383446415143
104339524663577060
165752696285769480
257568908011296119101
35928311199138119148126
5011099133118168144180153
701391251681492134184232196
95167150201179258223282238
120192172232206299259328276
150219196258225344299379319
185248223294255392341434364
240291261344297461403514430
300334298394339530464593497
400--470402634557715597

Table 4D3A PVC Insulation / Copper / Single-core / Armoured - IEE

  • Standard: BS 7671
  • Table 4D3A
  • Single-core armoured 70 °C thermoplastic insulated cables
  • Copper conductors
  • Conductor temperature: 70 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method C
(clipped direct)
Reference Method F
(in free air or in perforated cable tray horizontal or vertical)
TouchingTouchingSpaced by one cable diameter
2 cables,
single-
phase
AC or DC flat
3 or 4
cables,
three-
phase AC flat
2 cables,
single-
phase
AC or DC flat
3 cables,
three-
phase AC flat
3 cables,
three-
phase AC trefoil
2 DC cables2 AC cables
single-phase AC
3 or 4 cables
three-phase AC
HorizontalVerticalHorizontalVerticalHorizontalVertical
12345678 91011
123456789101112
50193179205189181229216229217230212
70245225259238231294279287272286263
95296269313285280357340349332338313
120342309360327324415396401383385357
150393352413373373479458449429436405
185447399469422425548525511489490456
240525465550492501648622593568566528
300594515624547567748719668640616578
400687575723618657885851737707674632
5007636228056737311035997810777721676
63084366989172880912181174893856771723
80091971097677788614411390943905824772
10009757371041808945168516271008967872816

Table 4D4A PVC Insulation / Copper / Multi-core / Armoured - IEE

  • Standard: BS 7671
  • Table 4D4A
  • Multi-core armoured 70 °C thermoplastic insulated cables
  • Copper conductors
  • Conductor temperature: 70 °C
  • Air Ambient temperature: 30 °C
  • Ground Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method C
(Clipped direct)
Reference Method E
(in free air or
in perforated cable tray
horizontal or vertical)
Reference Method F
(direct in ground or in ducting
in ground, in or around buildings)
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
123456
1234567
1.5211822192218
2.5282531262924
4383341353730
6494253454638
106758726260507
16897797837864
251181021281109982
3514512515713511998
50175151190163140116
70222192241207173143
95269231291251204169
120310267336290231192
150356306386332261217
185405348439378292243
240476409516445336280
300547469592510379316
400621540683590--

Table 4E1A XLPE Insulation / Copper / Single-core / Non-armoured - IEE

  • Standard: BS 7671
  • Table 4E1A
  • Single-core 90 °C thermosetting insulated cables, non armoured, with or without sheath
  • Copper conductors
  • Conductor temperature: 90 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method A
(enclosed in conduit
in thermally insulated
wall etc.)
Reference Method B
(enclosed in conduit
on a wall or in
trunking etc.)
Reference Method C
(Clipped direct)
Reference Method F
(in free air or in perforated cable tray horizontal or vertical)
TouchingSpaced
by one diameter
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
flat
3 cables,
three-
phase AC
flat
3 cables,
three-
phase AC
trefoil
2 single-phase cables
AC or DC or 3 cables
three-phase AC flat
HorizontalVertical
1234567891011
123456789101112
1141317151917.5-----
1.5191723202523-----
2.5262331283431-----
4353142374641-----
6454054485954-----
10615475668174-----
1681731008810999-----
2510695133117143130161141135182161
35131117164144176161200176169226201
50158141198175228209242216207275246
70200179253222293268310279268353318
95241216306269355326377342328430389
120278249354312413379437400383500454
150318285393342476436504464444577527
185362324449384545500575533510661605
240424380528450644590679634607781719
300486435603514743681783736703902833
400--68358486879394086882310851008
500--783666990904108399894612531169
630--9007641130103312541151108814541362
800----1288117913581275121415811485
1000----1443132315201436134917751671

Table 4E2A XLPE Insulation / Copper / Multi-core / Non-armoured - IEE

  • Standard: BS 7671
  • Table 4E2A
  • Multi-core 90 °C thermosetting insulated and thermoplastic sheathed cables, non armoured
  • Copper conductors
  • Conductor temperature: 90 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method A
(enclosed in conduit
in thermally insulated
wall etc.)
Reference Method B
(enclosed in conduit
on a wall or in
trunking etc.)
Reference Method C
(Clipped direct)
Reference Method E
(in free air or
in perforated cable tray
horizontal or vertical)
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
12345678
123456789
114.513171519172118
1.518.516.52219.524222623
2.52522302633303632
43330403545404942
64238514458526354
105751696080718675
167668918010796115100
259989119105138119149127
35121109146128171147185158
50145130175154209179225192
70183164221194269229289246
95220197265233328278352298
120253227305268382322410346
150290259334300441371473399
185329295384340506424542456
240386346459398599500641538
300442396532455693576741621
400--625536803667865741

Table 4E3A XLPE Insulation / Copper / Single-core / Armoured - IEE

  • Standard: BS 7671
  • Table 4E3A
  • Single-core armoured 90 °C thermosetting insulated cables
  • Copper conductors
  • Conductor temperature: 90 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method C
(clipped direct)
Reference Method F
(in free air or in perforated cable tray horizontal or vertical)
TouchingTouchingSpaced by one cable diameter
2 cables,
single-
phase
AC or DC flat
3 or 4
cables,
three-
phase AC flat
2 cables,
single-
phase
AC or DC flat
3 cables,
three-
phase AC flat
3 cables,
three-
phase AC trefoil
2 DC cables2 AC cables
single-phase AC
3 or 4 cables
three-phase AC
HorizontalVerticalHorizontalVerticalHorizontalVertical
1 2 345678 9 10 11
123456789101112
50237220253232222284270282266288266
70303277322293285356349357337358331
95367333389352246446426436412425393
120425383449405402519497504477485449
150488437516462463600575566539549510
185557496587524529688660643614618574
240656579689612625815782749714715666
300755662792700720943906842805810755
40085371789976781511371094929889848797
5009627911016851918131412661032989923871
6301082861114693510271528147411391092992940
80011709041246987111918091744120411551042978
10001261961134510551214210020261289123811101041

Table 4E4A XLPE Insulation / Copper / Multi-core / Armoured - IEE

  • Standard: BS 7671
  • Table 4E4A
  • Multi-core armoured 90 °C thermosetting insulated cables
  • Copper conductors
  • Conductor temperature: 90 °C
  • Air Ambient temperature: 30 °C
  • Ground Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method C
(Clipped direct)
Reference Method E
(in free air or
in perforated cable tray
horizontal or vertical)
Reference Method F
(direct in ground or in ducting
in ground, in or around buildings)
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
123456
1234567
1.5272329252521
2.5363139333328
4494252444336
6625366565344
10857390787158
1611094115999175
2514612415213111696
35180154188162139115
50219187228197164135
70279238291251203167
95338289354304239197
120392335410353271223
150451386472406306251
185515441539463343281
300698599732628446365
400787673847728--

Table 4H1A PVC Insulation / Aluminium / Single-core / Non-armoured - IEE

  • Standard: BS 7671
  • Table 4H1A
  • Single-core 70 °C thermoplastic insulated cables, non armoured, with or without sheath
  • Aluminium conductors
  • Conductor temperature: 70 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method A
(enclosed in conduit
in thermally insulated
wall etc.)
Reference Method B
(enclosed in conduit
on a wall or in
trunking etc.)
Reference Method C
(Clipped direct)
Reference Method F
(in free air or in perforated cable tray horizontal or vertical)
TouchingSpaced
by one diameter
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
flat
3 cables,
three-
phase AC
flat
3 cables,
three-
phase AC
trefoil
2 single-phase cables
AC or DC or 3 cables
three-phase AC flat
HorizontalVertical
1234567891011
123456789101112
509384118104125110149133128169152
70118107150133160140192173166217196
95142129181161195170235212203265241
120164149210186226197273247237308282
150189170234204261227316287274356327
185215194266230298259363330316407376
240252227312269352305430392375482447
300289261358306406351497455434557519
380--413352511472543502507625584
480--477405591546629582590726680
600--545462679626722669680837787
740----771709820761776956902
960----90082395388690711251066
1200----10229261073999102612931229

Table 4H2A PVC Insulation / Aluminium / Multi-core / Non-armoured - IEE

  • Standard: BS 7671
  • Table 4H2A
  • Multi-core 70 °C thermoplastic insulated and thermoplastic sheathed cables, non armoured
  • Aluminium conductors
  • Conductor temperature: 70 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method A
(enclosed in conduit
in thermally insulated
wall etc.)
Reference Method B
(enclosed in conduit
on a wall or in
trunking etc.)
Reference Method C
(Clipped direct)
Reference Method E
(in free air or
in perforated cable tray
horizontal or vertical)
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
12345678
123456789
164441544866597361
255853716283738978
35716586771039011196
50867810492125110135117
7010898131116160140173150
95130118157139195170210183
120-135-160-197-212
150-155-176-227-245
185-176-199-259280
240-207-232-305-330
300-237-265-351-381

Table 4H3A PVC Insulation / Aluminium / Single-core / Armoured - IEE

  • Standard: BS 7671
  • Table 4H3A
  • Single-core armoured 70 °C thermoplastic insulated cables
  • Aluminium conductors
  • Conductor temperature: 70 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method C
(clipped direct)
Reference Method F
(in free air or in perforated cable tray horizontal or vertical)
TouchingTouchingSpaced by one cable diameter
2 cables,
single-
phase
AC or DC flat
3 or 4
cables,
three-
phase AC flat
2 cables,
single-
phase
AC or DC flat
3 cables,
three-
phase AC flat
3 cables,
three-
phase AC trefoil
2 DC cables2 AC cables
single-phase AC
3 or 4 cables
three-phase AC
HorizontalVerticalHorizontalVerticalHorizontalVertical
12345678 9 10 11
123456789101112
50143133152141131167157168159169155
70183168194178168214202212200213196
95221202234214205261247259245255236
120255233270246238303288299285293272
150294267310282275349333340323335312
185334303352319315400382389371379354
240393354413374372472452457437443415
300452405474427430545523520498505475
380518452543479497638613583559551518
480586501616534568742715655629604568
600658550692589642859828724696656618
740728596769642715986952802770707666
96081965186870680811711133866832770726
120089369295275688013601317938902822774

Table 4H4A PVC Insulation / Aluminium / Multi-core / Armoured - IEE

  • Standard: BS 7671
  • Table 4H4A
  • Multi-core armoured 70 °C thermoplastic insulated cables
  • Aluminium conductors
  • Conductor temperature: 70 °C
  • Air Ambient temperature: 30 °C
  • Ground Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method C
(Clipped direct)
Reference Method E
(in free air or
in perforated cable tray
horizontal or vertical)
Reference Method F
(direct in ground or in ducting
in ground, in or around buildings)
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
123456
1234567
1668587161--
25897694807764
3510994115999377
5013111313911910991
70165143175151135112
95199174211186159132
120-202-216-1502
150-232-250-169
185-265-287-190
240-312-342-218
300-360-399-247

Table 4J1A XLPE Insulation / Aluminium / Single-core / Non-armoured - IEE

  • Standard:BS 7671
  • Table 4J1A
  • Single-core 90 °C thermosetting insulated cables, non armoured, with or without sheath
  • Aluminium conductors
  • Conductor temperature: 90 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method A
(enclosed in conduit
in thermally insulated
wall etc.)
Reference Method B
(enclosed in conduit
on a wall or in
trunking etc.)
Reference Method C
(Clipped direct)
Reference Method F
(in free air or in perforated cable tray horizontal or vertical)
TouchingSpaced
by one diameter
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
3 or 4
cables,
three-
phase AC
2 cables,
single-
phase
AC or DC
flat
3 cables,
three-
phase AC
flat
3 cables,
three-
phase AC
trefoil
2 single-phase cables
AC or DC or 3 cables
three-phase AC flat
HorizontalVertical
1234567891011
123456789101112
50125113157140154136184165159210188
70158142200179198174237215206271244
95191171242217242211289264253332300
120220197281251280245337308296387351
150253226307267324283389358343448408
185288256351300371323447413395515470
240338300412351439382530492471611561
300387344471402508440613571544708652
380----658594679628638798742
480----765692786728743927865
600----8717919038368491058990
740----1001911102595197912181143
960----1176107211911108115114401355
1200----1333121713411249130716431550

Table 4J2A XLPE Insulation / Aluminium / Multi-core / Non-armoured - IEE

  • Standard: BS 7671
  • Table 4J2A
  • Multi-core 90 °C thermosetting insulated and thermoplastic sheathed cables, non armoured
  • Aluminium conductors
  • Conductor temperature: 90 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method A
(enclosed in conduit
in thermally insulated
wall etc.)
Reference Method B
(enclosed in conduit
on a wall or in
trunking etc.)
Reference Method C
(Clipped direct)
Reference Method E
(in free air or
in perforated cable tray
horizontal or vertical)
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
12345678
123456789
166055726484769177
25787194841019010897
359687115103126112135120
50115104138124154136164146
70145131175156198174211187
95175157210188241211257227
120-180-216-245-263
150-206-240-283-304
185-233-272-323-347
240-273-318-382-409
300-313-364-440-471

Table 4J3A XLPE Insulation / Aluminium / Single-core / Armoured - IEE

  • Standard: BS 7671
  • Table 4J3A
  • Single-core armoured 90 °C thermosetting insulated cables
  • Aluminium conductors
  • Conductor temperature: 90 °C
  • Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method C
(clipped direct)
Reference Method F
(in free air or in perforated cable tray horizontal or vertical)
TouchingTouchingSpaced by one cable diameter
2 cables,
single-
phase
AC or DC flat
3 or 4
cables,
three-
phase AC flat
2 cables,
single-
phase
AC or DC flat
3 cables,
three-
phase AC flat
3 cables,
three-
phase AC trefoil
2 DC cables2 AC cables
single-phase AC
3 or 4 cables
three-phase AC
HorizontalVerticalHorizontalVerticalHorizontalVertical
12345678 9 10 11
123456789101112
50179165192176162216197212199215192
70228209244222207275253269254270244
95276252294267252332307328310324296
120320291340308292384357378358372343
150368333390352337441411429409424394
185419378444400391511480490467477447
240494443521468465605572576549554523
300568508597536540701666654624626595
380655573688608625812780735704693649
480747642786685714942906825790765717
60083670688075780110761036909872832780
740934764988824897125012051204989890835
9601056838112191110141488143510941052970911
120011639031236990111817151658118711411043980

Table 4J4A XLPE Insulation / Aluminium / Multi-core / Armoured - IEE

  • Standard: BS 7671
  • Table 4J4A
  • Multi-core armoured 90 °C thermosetting insulated cables
  • Aluminium conductors
  • Conductor temperature: 90 °C
  • Air Ambient temperature: 30 °C
  • Ground Ambient temperature: 30 °C
Conductor
nominal
cross-
sectional
area
[mm²]
Current-carrying capacities in [A]
Reference Method C
(Clipped direct)
Reference Method E
(in free air or
in perforated cable tray
horizontal or vertical)
Reference Method F
(direct in ground or in ducting
in ground, in or around buildings)
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
1 two-core
cable,single-phase
AC or DC
1 three-core
cable or
1 four-core
cable
three-phase
AC
123456
1234567
16827185747159
2510892112989075
3513211313812010890
50159137166145128106
70201174211185158130
95242214254224186154
120-249-264-174
150-284-305-197
185-328-350-220
240-386-418-253
300-441-488-286