Lowest allowed bending radius – Lowest allowed bending radius – in accordance with DIN VDE 0298 part 3

Lowest allowed bending radius in accordance with DIN VDE 0298 part 3 Nominal voltage up to 0,6 / 1kV

Outer diameter of cable / Thickness of flat cable in mm
Cables for fixed installation up to
10 mm
over/up to
10-25 mm
over
25 mm
for fixed installation 4 x d 4 x d 4 x d
for internal wiring 1 x d 2 x d 3 x d

 

 

Flexible cables Outer diameter of cable / Thickness of flat cable in mm
up to              over/up to          over/up to         over
8 mm              8-12 mm             12-20 mm           20 mm
for fixed installation 3 x d 3 x d 4 x d 4 x d
at free movement 3 x d 4 x d 5 x d 5 x d
at introduction 3 x d 4 x d 5 x d 5 x d
Flexible cables
at restricted guidance
Outer diameter of cable / Thickness of flat cable in mm
up to              over/up to          over/up to         over
8 mm              8-12 mm             12-20 mm           20 mm
Drum operation 5 x d 5 x d 5 x d 6 x d
Cable trolley operation 3 x d 4 x d 5 x d 5 x d
Drag chain operation 4 x d 4 x d 5 x d 5 x d
Roller deviation 8 x d 8 x d 8 x d 8 x d